Yaskawa VFD Fault Codes (V1000, A1000, GA700): Fault List & Fixes

Yaskawa V1000, A1000 & GA700 fault code list (oC, ov, Uv1, GF, oH1, oL1, LF, Hbb): Megger test procedures, IGBT checks & motor FLA calculator.

Showing 8 of 8 Yaskawa fault codes

Fault Code Drive Series Fault / Alarm Category Common Plant Causes Multimeter / Megger Check Spare Part / Fix
oC GA700 / A1000 / V1000 Overcurrent Overcurrent Output current exceeded hardware trip level (~200% rated) from phase short, rapid load impact, or blown IGBT. Disconnect motor leads; Megger windings >= 100 MOhm; diode-check IGBT bridge U/V/W to +1/- terminals. IGBT module, gate drive board, motor cable, or motor rewind.
ov GA700 / A1000 / V1000 DC Bus Overvoltage DC Bus Voltage DC bus exceeded ~410 V (200 V class) or ~820 V (400 V class) from regen decel, surge, or open braking resistor. Monitor U1-07 DC bus voltage; check input RMS mains; ohm-test braking resistor on B1/B2. Braking resistor, braking transistor, or input AC reactor.
Uv1 GA700 / A1000 / V1000 DC Bus Undervoltage DC Bus Voltage DC bus dropped below ~190 V (200 V) / ~380 V (400 V) from mains dip, missing phase, or failed soft-charge relay. Measure R/S/T input voltage; listen for soft-charge relay pull-in; check DC bus cap ESR. Soft-charge resistor/contactor, input fuse, or DC bus capacitors.
GF GA700 / A1000 / V1000 Ground Fault Earth/Phase Loss Ground leakage > 50% of drive rated output current caused by insulation failure or moisture ingress. Disconnect motor leads; Megger cable and motor separately at 1000 VDC; inspect junction box. Motor cable, stator insulation repair, or internal Hall current sensor.
oH1 GA700 / A1000 / V1000 Heatsink Overheat Thermal/Overload Heatsink temperature exceeded 90-105 deg C due to dead cooling fan, clogged heatsink, or high ambient temp. Check cooling fan operation and U4-08 heatsink temp; clean cooling fins and cabinet filters. Yaskawa OEM cooling fan kit or panel filter / air conditioner.
oL1 / oL2 GA700 / A1000 / V1000 Motor / Drive Overload Thermal/Overload Continuous operation above motor FLA (oL1) or VFD rating (oL2); wrong motor rated amps E2-01. Verify clamp-on amps on U/V/W; confirm E2-01 matches motor nameplate; check mechanical drag. Mechanical load service, motor cooling fan, or VFD upsizing.
LF GA700 / A1000 / V1000 Output Phase Loss Earth/Phase Loss Open circuit in one motor output phase, loose terminal, or corroded motor isolator contact. Check phase-to-phase Ohms at VFD U/V/W terminals (with LOTO); check clamp-on current balance. Motor cable termination, output disconnect switch, or motor stator.
Hbb / HbbF GA700 / A1000 / V1000 Safe Disable / STO Input Open Control/STO Safe Disable hardware inputs H1/H2 open (normal safety stop) or single-channel fault (HbbF). Check 24 VDC on H1 and H2 relative to HC; test safety relay dual contacts for simultaneous switching. Safety relay, safety wiring, or terminal board.

Yaskawa Field Diagnostic Protocol (LOTO, Megger & IGBT Test)

  1. Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
  2. Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Yaskawa output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
  3. Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
  4. IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Live Interactive Calculator · SI Metric & US Imperial

Electric Motor FLA, Starter & Overload Sizing Calculator

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

V

cos φ

%


Results

Full-load current (FLA)
—
A

Starting peak current
—
A

Overload relay setting (1.05× FLA)
—
A

Min. AC-3 contactor rating (1.25× FLA)
—
A

Input apparent power
—
kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

What should I check when Yaskawa A1000 / GA700 trips on oC Overcurrent?

Disconnect U/V/W motor cables, Megger windings at 1000 VDC (>= 100 MOhm), measure phase-to-phase Ohms, and diode-test the IGBT power bridge between U/V/W and +1/- terminals.

How do I resolve Yaskawa oL1 Motor Overload vs oL2 Drive Overload?

oL1 protects the motor (verify E2-01 motor rated FLA matches nameplate and clamp-check current); oL2 protects the VFD itself from running above drive capacity.

What does Yaskawa Hbb / HbbF Safe Disable mean?

Hbb indicates Safe Disable inputs H1/H2 are open (normal E-stop); HbbF indicates a dual-channel timing/wiring fault between H1 and H2 relative to HC.