Electric Motor FLA, Starter & Overload Sizing Calculator

No sign-up · calculates in your browser

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool Formula, worked example and FAQs below · results update as you type
V
cos φ
%

Results

Full-load current (FLA)
— A
Starting peak current
— A
Overload relay setting (1.05× FLA)
— A
Min. AC-3 contactor rating (1.25× FLA)
— A
Input apparent power
— kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Formula used

Three-phase FLA = (PkW × 1000) ÷ (√3 × V × cos φ × η). Single-phase removes the √3 factor.

Starting peak current depends on starter: DOL ≈ 6.5× FLA, Soft-Starter ≈ 3.0×, Star-Delta ≈ 2.2×, VFD ≈ 1.5×.

How to use this calculator

  1. Select 3-phase or 1-phase supply and enter motor shaft kW/HP.
  2. Enter supply voltage, nameplate power factor and efficiency.
  3. Choose the starting method to compare inrush amps and contactor sizing.
  4. Size feeder cables using our <a href="/cable-voltage-drop-calculator/">Cable Sizing & Voltage Drop Calculator</a>.

Worked example

A 15 kW, 415 V, 3-phase motor (cos φ = 0.85, η = 91 %) draws 27.0 A FLA. With Star-Delta starting, peak line current drops from 175 A (DOL) to 59.4 A; set overload around 28.3 A.

Frequently asked questions

Where should the thermal overload relay be placed in a Star-Delta starter?

If installed inside the delta branch (with the main contactor), set the relay to 0.58 × FLA (FLA ÷ √3). If installed on the main incoming line, set it to 1.0–1.05 × FLA.

At what motor power do plants switch from DOL to Star-Delta or Soft-Starter?

Most industrial plants restrict DOL starting to 7.5–11 kW on 415 V grids to avoid voltage dip on adjacent drives and switchgear.

Why use AC-3 contactor ratings for motors?

IEC AC-3 duty covers breaking full-load or stalled squirrel-cage motor currents safely; resistive AC-1 ratings cannot handle motor inductive switching arcs.