Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Results
- Full-load current (FLA)
- A
- Starting peak current
- A
- Overload relay setting (1.05× FLA)
- A
- Min. AC-3 contactor rating (1.25× FLA)
- A
- Input apparent power
- kVA
Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.
Formula used
Three-phase FLA = (PkW × 1000) ÷ (√3 × V × cos φ × η). Single-phase removes the √3 factor.
Starting peak current depends on starter: DOL ≈ 6.5× FLA, Soft-Starter ≈ 3.0×, Star-Delta ≈ 2.2×, VFD ≈ 1.5×.
How to use this calculator
- Select 3-phase or 1-phase supply and enter motor shaft kW/HP.
- Enter supply voltage, nameplate power factor and efficiency.
- Choose the starting method to compare inrush amps and contactor sizing.
- Size feeder cables using our <a href="/cable-voltage-drop-calculator/">Cable Sizing & Voltage Drop Calculator</a>.
Worked example
A 15 kW, 415 V, 3-phase motor (cos φ = 0.85, η = 91 %) draws 27.0 A FLA. With Star-Delta starting, peak line current drops from 175 A (DOL) to 59.4 A; set overload around 28.3 A.
Frequently asked questions
Where should the thermal overload relay be placed in a Star-Delta starter?
If installed inside the delta branch (with the main contactor), set the relay to 0.58 × FLA (FLA ÷ √3). If installed on the main incoming line, set it to 1.0–1.05 × FLA.
At what motor power do plants switch from DOL to Star-Delta or Soft-Starter?
Most industrial plants restrict DOL starting to 7.5–11 kW on 415 V grids to avoid voltage dip on adjacent drives and switchgear.
Why use AC-3 contactor ratings for motors?
IEC AC-3 duty covers breaking full-load or stalled squirrel-cage motor currents safely; resistive AC-1 ratings cannot handle motor inductive switching arcs.