Calculate direct steam boiler thermal efficiency, steam-to-fuel evaporation ratio, thermal duty (MW) and fuel heat input.
Results
- Direct boiler efficiency
- %
- Evaporation ratio (steam / fuel)
- kg/kg
- Boiler thermal output
- Fuel heat input
Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.
Formula used
Feedwater enthalpy hf ≈ 4.186 × Tfw [kJ/kg]. Direct efficiency η = [ṁs × (hg − hf)] ÷ [ṁf × GCV] × 100 %.
Evaporation ratio = ṁs ÷ ṁf [kg steam per kg fuel].
How to use this calculator
- Enter measured steam flow and enthalpy from the steam table at boiler pressure.
- Enter feedwater inlet temperature (after economizer if fitted).
- Enter fuel GCV from lab test or supplier spec and measured fuel flow.
- Track evaporation ratio daily to spot scaling, excess air or fouled heat-transfer tubes.
Worked example
Producing 5,000 kg/h of 10 bar g steam (2778 kJ/kg) from 85 °C feedwater using 380 kg/h of furnace oil (GCV 42,000 kJ/kg) gives 75.9 % efficiency and an evaporation ratio of 13.16 kg/kg.
Frequently asked questions
What is the difference between direct and indirect boiler efficiency?
Direct efficiency divides measured steam heat output by fuel heat input. Indirect efficiency measures stack gas, blowdown, radiation and unburnt losses and subtracts them from 100 % — it is more accurate when steam or fuel meters drift.
How much fuel does raising feedwater temperature by 6 °C save?
Every 6 °C rise in feedwater temperature via condensate return or an economizer saves roughly 1 % of boiler fuel consumption.
Why is GCV efficiency lower than NCV efficiency?
GCV (Higher Heating Value) includes latent heat of water vapour formed during combustion; because flue gas leaves above dew point, GCV-based efficiency is 5–10 % lower than NCV-based efficiency.