New in the library Presented by Jaadu Digital ↗
Free Business Profile Free tools

Free engineering tool · verified formulas

Motor Torque, Power & RPM Calculator

No sign-up · calculates in your browser

Convert motor power and speed to shaft torque, or torque to power, and estimate full-load current for three-phase and single-phase motors.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

rpm

V

cos φ

Typical 0.80–0.88 at full load

%

IE2 ≈ 88–91 %, IE3 ≈ 90–93 % at 7.5 kW



Results

Shaft torque
—

Shaft power
—

Electrical input
—
kW

Full-load current (est.)
—
A

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement
Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Formula used

T [N·m] = 9549.3 × P [kW] ÷ n [rpm]  ·  P = T × n ÷ 9549.3

Three-phase current: I = Pin × 1000 ÷ (√3 × V × cos φ), where Pin = P ÷ η. Single-phase: I = Pin × 1000 ÷ (V × cos φ).

The constant 9549.3 is 60 000 ÷ 2π: it converts rpm to rad/s and W to kW.

How to use this calculator

  1. Choose whether you know the power or the torque.
  2. Enter shaft speed from the nameplate (synchronous speed minus slip).
  3. Add voltage, power factor and efficiency to estimate current for cable and protection sizing.
  4. Switch units on any field — results update instantly.

Worked example

A 7.5 kW, 4-pole motor runs at 1450 rpm. Torque = 9549.3 × 7.5 ÷ 1450 = 49.4 N·m. At 90 % efficiency the motor draws 8.33 kW; on a 415 V supply at power factor 0.85 the current is 8333 ÷ (1.732 × 415 × 0.85) = 13.6 A. Nameplate current will differ slightly because efficiency and power factor vary by make.


Interactive 3D
Centrifugal Blower
Direct-driven backward-curved centrifugal fan: watch air enter the eye, get flung outward by the impeller and leave tangentially through the volute.
Drag to rotate · scroll or pinch to zoom · tap a part to learn what it does

Size it: Fan & Blower Power Calculator with Fan Laws →

Frequently asked questions

Why is torque higher at lower speed for the same power?

Power is torque multiplied by angular speed. A 4-pole (1450 rpm) motor of the same kW produces about twice the torque of a 2-pole (2900 rpm) motor, which is why gearboxes trade speed for torque.

Can I use this current for MCCB or cable sizing?

Use it as a check only. Size protection from the motor nameplate full-load current and the applicable code (IEC 60364, IS 732 or NEC), including starting current and derating.

What is the difference between kW and hp?

1 metric hp = 0.7355 kW; 1 mechanical (imperial) hp = 0.7457 kW. This calculator uses the mechanical horsepower used on IEC/NEMA motor plates.