Calculate cooling tower range (ΔT), heat rejection (kW & TR), evaporation loss, blowdown rate and total makeup water requirement from circulation flow and COC.
Results
- Cooling range (ΔT)
- Heat rejection
- Evaporation loss (E)
- Blowdown loss (B)
- Total makeup water (M)
Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.
Formula used
Range ΔT = Thot − Tcold. Heat rejected Q = ṁ × 4.186 × ΔT [kW]. Evaporation E = 0.00085 × 1.8 × Flow × ΔT°C.
Blowdown B = E ÷ (COC − 1) − Drift. Total makeup water M = E + B + Drift = E × COC ÷ (COC − 1).
How to use this calculator
- Enter circulation pump flow and hot/cold water basin temperatures.
- Enter target Cycles of Concentration (COC) set by your water treatment program.
- Enter drift loss percentage from the drift eliminator spec.
- Use total makeup water to size the softener/RO plant and float valve.
Worked example
A 200 m³/h tower cooling from 37 °C to 32 °C (ΔT = 5 °C, COC = 4) rejects 1,163 kW (331 TR), evaporates 1.53 m³/h, blows down 0.47 m³/h and needs 2.04 m³/h total makeup.
Frequently asked questions
How much water does raising COC from 3 to 5 save?
At COC = 3, blowdown is 50 % of evaporation. Raising COC to 5 cuts blowdown to 25 % of evaporation, saving roughly 17 % of total makeup water and treatment chemicals.
What is the difference between cooling tower range and approach?
Range is hot inlet minus cold outlet water temperature (heat load across the process). Approach is cold outlet water minus ambient wet-bulb temperature (tower thermal efficiency).
Why is 1 TR of cooling tower capacity larger than 1 TR of chiller?
A water-cooled chiller rejects both the evaporator heat load and the compressor shaft power (~20–25 % extra), so cooling towers are typically rated around 4.4 kW per chiller ton.