Convert process temperature to IEC 60751 PT100/PT1000 resistance (Ω) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.
Results
- RTD resistance
- Ω
- Thermocouple EMF (vs 0 °C)
- mV
- 4–20 mA transmitter output
- mA
- Class A / Class 1 tolerance (±)
- °C
- Class B / Class 2 tolerance (±)
- °C
Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.
Formula used
IEC 60751 Callendar–Van Dusen (T ≥ 0 °C): R(T) = R0 × (1 + A·T + B·T²), where A = 3.9083×10−3 °C−1 and B = −5.775×10−7 °C−2.
4–20 mA loop current: I = 4 + 16 × (T − LRV) ÷ (URV − LRV). Class A RTD tolerance: ±(0.15 + 0.002|T|) °C.
How to use this calculator
- Choose PT100, PT1000, Type K or Type J sensor.
- Enter the measured process temperature in °C.
- Enter the transmitter 4 mA (LRV) and 20 mA (URV) range values.
- Compare resistance/mV and loop current against your multimeter or HART calibrator.
Worked example
A PT100 sensor at 150 °C reads 157.33 Ω (±0.45 °C Class A). On a 0–300 °C transmitter span, the loop current is 12.00 mA.
Frequently asked questions
When should I choose a 3-wire or 4-wire PT100 over 2-wire?
Use 3-wire RTDs for standard industrial PLC/transmitter runs to cancel lead resistance, and 4-wire RTDs for precision lab or custody-transfer measurements where every 0.385 Ω lead error shifts temperature by 1 °C.
Does cold-junction compensation matter when checking thermocouple mV?
Yes. The table value assumes a 0 °C reference junction. If your field terminal block is at 30 °C ambient, subtract the mV equivalent of 30 °C (~1.20 mV for Type K) when measuring with a plain millivoltmeter.
What is the difference between PT100 Class A and Class B?
Class A is roughly twice as accurate (±0.15 + 0.002|T| °C) as Class B (±0.30 + 0.005|T| °C) and is preferred for critical reactor, pasteurizer and HVAC chiller loops.