Danfoss VLT VFD Fault Codes (FC51, FC302): Alarms, Warnings & Fixes

Danfoss VLT FC51, FC202 & FC302 alarm troubleshooting chart: Alarm 14 Earth Fault, Alarm 13 Overcurrent, Alarm 7/8 DC bus, Alarm 68 Safe Stop & spares.

Showing 9 of 9 Danfoss fault codes

Fault Code Drive Series Fault / Alarm Category Common Plant Causes Multimeter / Megger Check Spare Part / Fix
Alarm 14 VLT FC 302 / FC 202 Earth (Ground) Fault Earth/Phase Loss Current leakage from U/V/W output phase to ground in motor stator, wet junction box, or long shielded cable. Disconnect motor leads at drive; Megger cable and motor separately (1000 VDC); check current sum on CT. Motor cable, waterproof cable gland, output dV/dt filter, or internal current sensor.
Alarm 13 VLT FC 302 / FC 202 Overcurrent Overcurrent Peak inverter current exceeded due to sudden shock load, phase-to-phase short, or incorrect AMA (Automatic Motor Adaptation). Check U/V/W resistance balance; Megger motor; spin shaft by hand; verify AMA was completed at cold motor. IGBT power card, motor cable, or mechanical coupling / driven shaft.
Alarm 7 VLT FC 302 / FC 202 DC Overvoltage DC Bus Voltage Intermediate circuit DC voltage exceeded limit (~820 VDC on 400 V) during fast stop or line overvoltage transient. Measure mains voltage and DC link readout; check brake resistor continuity if fitted. Brake resistor, brake IGBT module, or surge arrestor / line reactor.
Alarm 8 VLT FC 302 / FC 202 DC Undervoltage DC Bus Voltage Supply voltage dropped below minimum threshold, loose main contactor, or failing DC bus capacitors. Measure 3-phase input under load; inspect rectifier SCR/diode bridge and soft-charge resistor. Mains contactor, input fuses, or DC bus capacitor bank.
Alarm 16 VLT FC 302 / FC 202 Short Circuit Overcurrent Direct short between output phases or inside IGBT bridge triggering hardware desaturation protection. Isolate motor leads completely; check U-V, V-W, W-U with ohmmeter and diode-test VFD output to DC bus. IGBT power module / power card or motor stator replacement.
Alarm 9 VLT FC 302 / FC 202 Inverter Overload Thermal/Overload Drive running above 100% rated output current for > 60 s due to undersized VFD or mechanical overload. Clamp-check all 3 motor phase currents vs drive nameplate rating; inspect load torque. Mechanical load service or upsizing VFD to heavy-duty rating.
Alarm 10 / 11 VLT FC 302 / FC 202 Motor ETR / Thermistor Overtemp Thermal/Overload Motor running hot from continuous overload, blocked cooling fins, or open/tripped PTC thermistor in winding. Measure motor frame temp with IR thermometer; check PTC resistance (< 100 Ohm cold, > 3 kOhm hot) on thermistor input. Motor cooling fan cowl, PTC thermistor relay, or forced-ventilation blower.
Alarm 4 VLT FC 302 / FC 202 Mains Phase Imbalance / Loss Earth/Phase Loss Missing mains input phase, blown fuse on one leg, or > 3% voltage imbalance between L1/L2/L3. Measure L1-L2, L2-L3, L1-L3 RMS voltages at drive input; check upstream fuses and breaker poles. Input fuse link, MCCB contact block, or 3-phase line reactor.
Alarm 68 VLT FC 302 Safe Stop / STO Activated Control/STO 24 VDC removed from Terminal 37 (Safe Torque Off) via E-stop, guard switch, or broken control wire. Measure 24 VDC between Terminal 37 and Terminal 20 (GND); verify safety PLC / relay output. Safety relay, guard interlock switch, or 24 VDC control PSU.

Danfoss Field Diagnostic Protocol (LOTO, Megger & IGBT Test)

  1. Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
  2. Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Danfoss output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
  3. Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
  4. IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Live Interactive Calculator · SI Metric & US Imperial

Electric Motor FLA, Starter & Overload Sizing Calculator

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

V

cos φ

%


Results

Full-load current (FLA)
—
A

Starting peak current
—
A

Overload relay setting (1.05× FLA)
—
A

Min. AC-3 contactor rating (1.25× FLA)
—
A

Input apparent power
—
kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

How do I clear Danfoss VLT Alarm 14 Earth (Ground) Fault?

Lock out power, disconnect U/V/W motor leads from the VLT terminals, and Megger the motor and cable separately at 1000 VDC. Check motor terminal box for condensation and verify output dV/dt filter wiring if fitted.

Why does Danfoss FC302 show Alarm 7 DC Overvoltage?

Alarm 7 trips when intermediate DC link voltage exceeds ~820 VDC (on 400 V mains) during fast deceleration of high-inertia fans or centrifuges. Increase ramp-down time (Par 3-42) or check braking resistor continuity.

What triggers Danfoss Alarm 68 Safe Stop?

Alarm 68 activates when 24 VDC is removed from Terminal 37 (Safe Torque Off). Verify 24 VDC between Terminal 37 and Terminal 20 (GND) and inspect E-stop or safety relay contacts.