Delta MS300, VFD-E & C2000 VFD fault code decoder (ocA, ocd, ocn, ovA, LvA, oH1, GFF, PHL, STo): field multimeter checks, causes & motor FLA calculator.
Showing 10 of 10 Delta fault codes
| Fault Code | Drive Series | Fault / Alarm | Category | Common Plant Causes | Multimeter / Megger Check | Spare Part / Fix |
|---|---|---|---|---|---|---|
ocA |
MS300 / C2000 / VFD-E | Overcurrent During Acceleration | Overcurrent | Accel ramp time too short for load inertia, motor shorted at startup, or excessive low-frequency torque boost. | Megger motor at 1000 VDC; check U/V/W resistance balance; inspect load for mechanical bind on start. | Motor cable/winding repair, or IGBT module if drive trips with motor disconnected. |
ocd |
MS300 / C2000 / VFD-E | Overcurrent During Deceleration | Overcurrent | Decel time too short causing over-fluxing/current spike, or mechanical brake engaging before output shuts off. | Measure current during decel; verify external holding brake release/engage timing. | Brake resistor / chopper or mechanical brake contactor. |
ocn |
MS300 / C2000 / VFD-E | Overcurrent at Constant Speed | Overcurrent | Sudden process jam/slug load, transient cable short from vibration, or failing Hall current sensor. | Inspect motor clamp-on amps for spikes; Megger cable while flexing conduit; test drive with no motor. | Hall current sensor, IGBT module, or jammed pump/conveyor parts. |
ovA |
MS300 / C2000 / VFD-E | DC Bus Overvoltage | DC Bus Voltage | Regenerative energy pushing DC bus > 400 VDC (230 V) or > 800 VDC (460 V), or high incoming mains voltage. | Check mains RMS voltage; measure braking resistor Ohms between +1/B1 and B2. | Dynamic braking resistor, braking unit, or input AC reactor. |
LvA |
MS300 / C2000 / VFD-E | Low DC Bus Voltage (Undervoltage) | DC Bus Voltage | Mains brownout, missing phase, loose R/S/T terminal screw, or open soft-start charge resistor. | Measure R-S-T line voltages under start; inspect pre-charge relay click and DC bus voltage display. | Soft-charge resistor, relay, input fuse, or DC bus capacitors. |
oH1 |
MS300 / C2000 / VFD-E | Heatsink Overheat | Thermal/Overload | Heatsink cooling fan seized, dust-packed fins, ambient > 50 deg C, or faulty thermal sensor. | Check heatsink fan spinning speed; clean heatsink tunnels with dry compressed air; verify thermistor connection. | Cooling fan replacement, cabinet air filter, or thermal sensor. |
oL |
MS300 / C2000 / VFD-E | Motor / Drive Overload | Thermal/Overload | Output current exceeds electronic thermal relay curve (150% for 60 s) from high friction or undersized motor. | Check motor phase currents with true-RMS clamp; compare to motor nameplate FLA and drive Pr.06-xx. | Mechanical bearing/belt service or upsizing motor/VFD. |
GFF |
MS300 / C2000 / VFD-E | Ground Fault | Earth/Phase Loss | Leakage current to PE > 50% of drive rated current due to grounded motor phase or wet cable. | Disconnect U/V/W; Megger motor and cable at 1000 VDC to earth; test VFD unloaded to rule out faulty CT. | Motor stator rewind, power cable replacement, or Hall CT board. |
PHL |
MS300 / C2000 | Input Phase Loss | Earth/Phase Loss | Open phase on R/S/T input, excessive DC bus ripple from failing capacitors, or unbalanced utility supply. | Check 3-phase input voltage balance (< 2%); inspect DC bus capacitors for bulging/leakage. | Upstream fuse/contactor or DC bus electrolytic capacitor kit. |
STo / STL1 |
MS300 / C2000 | Safe Torque Off / Safety Open | Control/STO | S1/S2 safety terminals open from E-stop circuit, or internal safety channel discrepancy (STL1/STL2). | Measure 24 VDC at S1 and S2 against DCM; verify jumper or dual-channel safety relay. | Safety relay, E-stop switch, or control terminal board. |
No matching rows found. Clear the search box or switch back to All.
Delta Field Diagnostic Protocol (LOTO, Megger & IGBT Test)
- Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
- Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Delta output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
- Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
- IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Electric Motor FLA, Starter & Overload Sizing Calculator
Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Frequently Asked Questions
What is the difference between Delta ocA, ocd, and ocn faults?
ocA is overcurrent during acceleration (shorted cable, mechanical bind, or too-fast accel ramp), ocd is overcurrent during deceleration (brake timing or over-fluxing), and ocn is overcurrent at constant speed (process jam or transient cable fault).
How do I troubleshoot Delta GFF Ground Fault on MS300 or C2000?
Disconnect U/V/W at the drive and Megger the motor and cable to earth at 1000 VDC. If the drive still trips GFF with motor leads disconnected, inspect the internal Hall-effect CT board.
Why does Delta VFD display STo or STL1?
STo indicates Safe Torque Off is active because 24 VDC is missing on S1/S2 relative to DCM. STL1 indicates a discrepancy between internal safety channels S1 and S2.