New in the library Presented by Jaadu Digital ↗
Free tools

Siemens SINAMICS VFD Fault Codes (G120, V20): Alarm & Fix Chart

Siemens SINAMICS G120, V20 & MM440 fault code list (F0001, F30001, F30021, F07801, F01600): root causes, Megger checks, spare parts & motor FLA sizing.

Showing 10 of 10 Siemens fault codes

Fault Code Drive Series Fault / Alarm Category Common Plant Causes Multimeter / Megger Check Spare Part / Fix
F0001 / F30001 SINAMICS G120 / MM440 Overcurrent Overcurrent Motor power exceeds drive rating, short circuit in U/V/W leads, too short ramp-up time, or faulty current measurement. Disconnect motor cable; Megger test motor windings >= 100 MOhm; check phase resistance symmetry; test power module IGBTs. Power Module (PM240-2) IGBT stack, motor cable, or Hall CT sensor.
F0002 / F30002 SINAMICS G120 / MM440 DC Link Overvoltage DC Bus Voltage Regenerative braking energy from high-inertia load, high mains supply voltage, or missing braking resistor. Check r0026 DC link voltage; measure supply L1-L2-L3; verify braking resistor resistance and chopper duty. Braking resistor, braking module, or line choke.
F0003 / F30003 SINAMICS G120 / MM440 DC Link Undervoltage DC Bus Voltage Supply outage, phase failure, undersized supply transformer causing dip on start, or defective pre-charge circuit. Verify 3-phase input voltage at terminals under load; check DC link voltage r0026 against 1.35 x Vrms. Input fuse, pre-charge resistor/relay, or DC link capacitor bank.
F0004 SINAMICS G120 / MM440 Inverter Overtemperature Thermal/Overload Blocked heatsink airflow, dead cooling fan, high ambient cabinet temperature, or excessive pulse frequency. Check cooling fan airflow and r0037 heatsink temperature; verify panel cooling/AC unit operation. PM240 cooling fan assembly, cabinet filter media, or NTC thermistor.
F0011 / F07011 SINAMICS G120 / MM440 Motor I2t / Overtemperature Thermal/Overload Continuous overload above motor FLA, blocked motor cooling cowl/fan, low-speed torque overload without forced cooling, or open PTC/KTY84. Measure motor RMS current with clamp meter; verify motor cooling fan; measure PTC/PT1000 sensor Ohms across T1/T2. Motor auxiliary blower fan, PTC/KTY thermistor sensor, or motor upsizing.
F0022 MM440 / SINAMICS Powerstack / UCE Hardware Overcurrent Overcurrent Instantaneous IGBT desaturation (UCE) trip from dead short on output, failed gate drive optocoupler, or internal IGBT fault. Megger motor and cable disconnected from drive; check IGBT legs with diode mode; inspect gate drive ribbon cable. IGBT power module, gate driver board, or complete SINAMICS power module.
F07801 SINAMICS G120 Motor Overcurrent Overcurrent Exceeded p0640 current limit due to jammed load, incorrect motor data p0305-p0310, or V/Hz boost set too high. Inspect driven machine for binding; verify motor nameplate parameters in drive and run stationary/rotating ID. Mechanical coupling/gearbox repair or motor current sensor board.
F07900 SINAMICS G120 Motor Blocked / Stalled Thermal/Overload Motor remains at torque/current limit beyond p2177 stall delay due to seized mechanical load or closed discharge damper/valve. Check mechanical shaft rotation; inspect encoder/speed feedback if closed-loop; check clamp-on phase currents. Encoder / coupling / driven machine bearings or brake release coil.
F30021 SINAMICS G120 Ground / Earth Fault Earth/Phase Loss Earth leakage > threshold due to wet motor windings, damaged cable armor, or high-capacitance long cable run. Megger motor and cable separately at 1000 VDC; check shield grounding and PE continuity. Motor winding dry-out/rewind, motor cable, or sine-wave/dV/dt output filter.
F01600 / F30600 SINAMICS G120 STO / Safety Integrated Defect Control/STO Mismatch or timeout between dual-channel F-DI safety inputs, missing PROFIsafe heartbeat, or wiring fault on STO terminals. Measure 24 VDC on both safety channels; check safety relay timing discrepancy (< 50 ms) and grounding. Safety relay / F-DI terminal block or Control Unit (CU240E-2 / CU250S-2).

Siemens Field Diagnostic Protocol (LOTO, Megger & IGBT Test)

  1. Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
  2. Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Siemens output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
  3. Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
  4. IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Live Interactive Calculator · SI Metric & US Imperial

Electric Motor FLA, Starter & Overload Sizing Calculator

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

V

cos φ

%


Results

Full-load current (FLA)
—
A

Starting peak current
—
A

Overload relay setting (1.05× FLA)
—
A

Min. AC-3 contactor rating (1.25× FLA)
—
A

Input apparent power
—
kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

What causes Siemens SINAMICS F30001 / F0001 Overcurrent?

F30001/F0001 trips when output current exceeds the hardware limit due to shorted motor leads, seized driven equipment, wrong motor nameplate data (p0305-p0310), or blown PM240-2 IGBT module.

How do I troubleshoot Siemens F30021 Ground Fault on G120?

Disconnect U2/V2/W2 at the PM240 power module, Megger cable and motor separately at 1000 VDC to PE, inspect cable gland seals for moisture, and verify shield bonding on both ends.

What does Siemens F07900 Motor Blocked mean?

F07900 indicates the motor stayed at torque/current limit longer than stall delay p2177. Check for seized pump/gearbox bearings, closed discharge valve, or failed mechanical brake release.

Your saved guides

Saved only in this browser. No account required.

Advertisement