VFD Drive Fault Code Decoder & Breakdown Troubleshooter

Instant-search industrial VFD fault code decoder for ABB, Siemens, Danfoss, Delta, Schneider and Yaskawa drives with multimeter, Megger checks and spare parts.

Showing 55 of 55 industrial VFD fault codes

ABB2310 / F0001ACS580 / ACS880 / ACS550

Overcurrent

Overcurrent

Common Plant Causes
Short circuit in motor cable/winding, mechanical jam, overly aggressive acceleration ramp, or incorrect motor nameplate / ID run data.
Multimeter / Insulation Megger Check
Disconnect U/V/W from drive; Megger phases to PE at 1000 VDC (>= 100 MOhm); measure phase-to-phase Ohms (< 2% imbalance); check IGBT diode drop.
Spare Part / Fix Required
Motor power cable, IGBT power module, Hall-effect current transducer (CT), or motor rewinding.
ABB3210 / F0002ACS580 / ACS880 / ACS550

DC Bus Voltage

DC Bus Overvoltage

Common Plant Causes
High-inertia load regenerating during fast decel, mains voltage surge (> 480 VAC +10%), or open/failed dynamic braking resistor.
Multimeter / Insulation Megger Check
Measure incoming L1-L2-L3 RMS voltage and DC bus VDC (normal ~540-680 VDC on 400-480 V mains); check braking resistor Ohmic value against drive manual.
Spare Part / Fix Required
Dynamic braking resistor, braking chopper IGBT, or input AC line reactor.
ABB3220 / F0003ACS580 / ACS880 / ACS550

DC Bus Voltage

DC Bus Undervoltage

Common Plant Causes
Mains sag or momentary power dip, blown input fuse, loose breaker lug, or failed pre-charge resistor/contactor.
Multimeter / Insulation Megger Check
Measure L1-L2-L3 under load; inspect DC bus voltage on keypad; test input rectifier diodes and DC pre-charge contactor coil/resistor.
Spare Part / Fix Required
Semiconductor input fuses, pre-charge resistor, input rectifier bridge, or DC bus electrolytic capacitors.
ABB2330 / F0016ACS580 / ACS880 / ACS550

Earth/Phase Loss

Earth / Ground Fault

Common Plant Causes
Insulation breakdown in motor or submerged cable, moisture in terminal box, or excessive cable capacitance at high switching frequency.
Multimeter / Insulation Megger Check
Isolate cable from motor; Megger cable alone and motor alone at 500/1000 VDC to PE; inspect motor junction box for condensation.
Spare Part / Fix Required
Motor terminal block/gland seal, armoured motor cable, dV/dt output choke, or current sensor board.
ABB4210 / F0004ACS580 / ACS880 / ACS550

Thermal/Overload

IGBT / Drive Overtemperature

Common Plant Causes
Clogged panel air filters, failed internal heatsink cooling fan, ambient > 40-50 deg C, or excessive carrier frequency.
Multimeter / Insulation Megger Check
Check heatsink fan rotation and 24 VDC supply; inspect cabinet intake louvers and heatsink fins; read IGBT temp parameter in diagnostics.
Spare Part / Fix Required
Internal heatsink cooling fan, panel filter mats, cabinet exhaust fan, or thermal paste / NTC sensor.
ABB7121ACS580 / ACS880

Thermal/Overload

Motor Stall

Common Plant Causes
Mechanical rotor lock, seized pump/gearbox bearing, belt jam, or V/Hz torque boost too low at low speed.
Multimeter / Insulation Megger Check
Spin driven shaft manually (LOTO); measure motor phase amps with true-RMS clamp meter; verify gearbox oil and coupling.
Spare Part / Fix Required
Driven equipment bearings, coupling insert, or drive current-limit / stall supervision tuning.
ABBSTO / 5091ACS580 / ACS880

Control/STO

Safe Torque Off Active

Common Plant Causes
Safety relay/E-stop loop open, loose 24 VDC jumper on XSTO terminals, or single-channel discrepancy between STO1 and STO2.
Multimeter / Insulation Megger Check
Measure 24 VDC on both STO1 and STO2 inputs relative to 0 V / SGND; verify E-stop mushroom button and safety relay contacts.
Spare Part / Fix Required
Dual-channel safety relay, E-stop contact block, or XSTO plug connector.
ABB3130ACS580 / ACS880

Earth/Phase Loss

Input Phase Loss

Common Plant Causes
Blown upstream HRC fuse, tripped single-phase contactor contact, severe mains voltage unbalance (> 3%), or loose terminal lug.
Multimeter / Insulation Megger Check
Measure L1-L2, L2-L3, L1-L3 line voltages at drive input terminals with multimeter; check thermal discoloration on lugs.
Spare Part / Fix Required
Upstream HRC/gG input fuse, mains contactor contact kit, or input rectifier diode module.
ABB2340ACS580 / ACS880

Overcurrent

Output Short Circuit

Common Plant Causes
Dead short phase-to-phase in motor winding or junction box, or shorted output IGBT leg.
Multimeter / Insulation Megger Check
Isolate U/V/W leads; measure phase-to-phase resistance (should be symmetric); test U/V/W to +DC/-DC diodes on VFD.
Spare Part / Fix Required
IGBT power module, gate driver board, or motor stator rewind / cable replacement.
ABB5081ACS580 / ACS880

Thermal/Overload

Auxiliary Fan Fault

Common Plant Causes
Stalled cooling fan bearing, dust-jammed fan impeller, or broken fan tachometer feedback wire.
Multimeter / Insulation Megger Check
Check 24 VDC at fan connector; spin fan blades by hand for bearing drag; inspect tach wire continuity.
Spare Part / Fix Required
OEM VFD cooling fan kit (heatsink / control-board fan).
SiemensF0001 / F30001SINAMICS G120 / MM440

Overcurrent

Overcurrent

Common Plant Causes
Motor power exceeds drive rating, short circuit in U/V/W leads, too short ramp-up time, or faulty current measurement.
Multimeter / Insulation Megger Check
Disconnect motor cable; Megger test motor windings >= 100 MOhm; check phase resistance symmetry; test power module IGBTs.
Spare Part / Fix Required
Power Module (PM240-2) IGBT stack, motor cable, or Hall CT sensor.
SiemensF0002 / F30002SINAMICS G120 / MM440

DC Bus Voltage

Common Plant Causes
Regenerative braking energy from high-inertia load, high mains supply voltage, or missing braking resistor.
Multimeter / Insulation Megger Check
Check r0026 DC link voltage; measure supply L1-L2-L3; verify braking resistor resistance and chopper duty.
Spare Part / Fix Required
Braking resistor, braking module, or line choke.
SiemensF0003 / F30003SINAMICS G120 / MM440

DC Bus Voltage

Common Plant Causes
Supply outage, phase failure, undersized supply transformer causing dip on start, or defective pre-charge circuit.
Multimeter / Insulation Megger Check
Verify 3-phase input voltage at terminals under load; check DC link voltage r0026 against 1.35 x Vrms.
Spare Part / Fix Required
Input fuse, pre-charge resistor/relay, or DC link capacitor bank.
SiemensF0004SINAMICS G120 / MM440

Thermal/Overload

Inverter Overtemperature

Common Plant Causes
Blocked heatsink airflow, dead cooling fan, high ambient cabinet temperature, or excessive pulse frequency.
Multimeter / Insulation Megger Check
Check cooling fan airflow and r0037 heatsink temperature; verify panel cooling/AC unit operation.
Spare Part / Fix Required
PM240 cooling fan assembly, cabinet filter media, or NTC thermistor.
SiemensF0011 / F07011SINAMICS G120 / MM440

Thermal/Overload

Motor I2t / Overtemperature

Common Plant Causes
Continuous overload above motor FLA, blocked motor cooling cowl/fan, low-speed torque overload without forced cooling, or open PTC/KTY84.
Multimeter / Insulation Megger Check
Measure motor RMS current with clamp meter; verify motor cooling fan; measure PTC/PT1000 sensor Ohms across T1/T2.
Spare Part / Fix Required
Motor auxiliary blower fan, PTC/KTY thermistor sensor, or motor upsizing.
SiemensF0022MM440 / SINAMICS

Overcurrent

Powerstack / UCE Hardware Overcurrent

Common Plant Causes
Instantaneous IGBT desaturation (UCE) trip from dead short on output, failed gate drive optocoupler, or internal IGBT fault.
Multimeter / Insulation Megger Check
Megger motor and cable disconnected from drive; check IGBT legs with diode mode; inspect gate drive ribbon cable.
Spare Part / Fix Required
IGBT power module, gate driver board, or complete SINAMICS power module.
SiemensF07801SINAMICS G120

Overcurrent

Motor Overcurrent

Common Plant Causes
Exceeded p0640 current limit due to jammed load, incorrect motor data p0305-p0310, or V/Hz boost set too high.
Multimeter / Insulation Megger Check
Inspect driven machine for binding; verify motor nameplate parameters in drive and run stationary/rotating ID.
Spare Part / Fix Required
Mechanical coupling/gearbox repair or motor current sensor board.
SiemensF07900SINAMICS G120

Thermal/Overload

Motor Blocked / Stalled

Common Plant Causes
Motor remains at torque/current limit beyond p2177 stall delay due to seized mechanical load or closed discharge damper/valve.
Multimeter / Insulation Megger Check
Check mechanical shaft rotation; inspect encoder/speed feedback if closed-loop; check clamp-on phase currents.
Spare Part / Fix Required
Encoder / coupling / driven machine bearings or brake release coil.
SiemensF30021SINAMICS G120

Earth/Phase Loss

Ground / Earth Fault

Common Plant Causes
Earth leakage > threshold due to wet motor windings, damaged cable armor, or high-capacitance long cable run.
Multimeter / Insulation Megger Check
Megger motor and cable separately at 1000 VDC; check shield grounding and PE continuity.
Spare Part / Fix Required
Motor winding dry-out/rewind, motor cable, or sine-wave/dV/dt output filter.
SiemensF01600 / F30600SINAMICS G120

Control/STO

STO / Safety Integrated Defect

Common Plant Causes
Mismatch or timeout between dual-channel F-DI safety inputs, missing PROFIsafe heartbeat, or wiring fault on STO terminals.
Multimeter / Insulation Megger Check
Measure 24 VDC on both safety channels; check safety relay timing discrepancy (< 50 ms) and grounding.
Spare Part / Fix Required
Safety relay / F-DI terminal block or Control Unit (CU240E-2 / CU250S-2).
DanfossAlarm 14VLT FC 302 / FC 202

Earth/Phase Loss

Earth (Ground) Fault

Common Plant Causes
Current leakage from U/V/W output phase to ground in motor stator, wet junction box, or long shielded cable.
Multimeter / Insulation Megger Check
Disconnect motor leads at drive; Megger cable and motor separately (1000 VDC); check current sum on CT.
Spare Part / Fix Required
Motor cable, waterproof cable gland, output dV/dt filter, or internal current sensor.
DanfossAlarm 13VLT FC 302 / FC 202

Overcurrent

Overcurrent

Common Plant Causes
Peak inverter current exceeded due to sudden shock load, phase-to-phase short, or incorrect AMA (Automatic Motor Adaptation).
Multimeter / Insulation Megger Check
Check U/V/W resistance balance; Megger motor; spin shaft by hand; verify AMA was completed at cold motor.
Spare Part / Fix Required
IGBT power card, motor cable, or mechanical coupling / driven shaft.
DanfossAlarm 7VLT FC 302 / FC 202

DC Bus Voltage

DC Overvoltage

Common Plant Causes
Intermediate circuit DC voltage exceeded limit (~820 VDC on 400 V) during fast stop or line overvoltage transient.
Multimeter / Insulation Megger Check
Measure mains voltage and DC link readout; check brake resistor continuity if fitted.
Spare Part / Fix Required
Brake resistor, brake IGBT module, or surge arrestor / line reactor.
DanfossAlarm 8VLT FC 302 / FC 202

DC Bus Voltage

DC Undervoltage

Common Plant Causes
Supply voltage dropped below minimum threshold, loose main contactor, or failing DC bus capacitors.
Multimeter / Insulation Megger Check
Measure 3-phase input under load; inspect rectifier SCR/diode bridge and soft-charge resistor.
Spare Part / Fix Required
Mains contactor, input fuses, or DC bus capacitor bank.
DanfossAlarm 16VLT FC 302 / FC 202

Overcurrent

Short Circuit

Common Plant Causes
Direct short between output phases or inside IGBT bridge triggering hardware desaturation protection.
Multimeter / Insulation Megger Check
Isolate motor leads completely; check U-V, V-W, W-U with ohmmeter and diode-test VFD output to DC bus.
Spare Part / Fix Required
IGBT power module / power card or motor stator replacement.
DanfossAlarm 9VLT FC 302 / FC 202

Thermal/Overload

Inverter Overload

Common Plant Causes
Drive running above 100% rated output current for > 60 s due to undersized VFD or mechanical overload.
Multimeter / Insulation Megger Check
Clamp-check all 3 motor phase currents vs drive nameplate rating; inspect load torque.
Spare Part / Fix Required
Mechanical load service or upsizing VFD to heavy-duty rating.
DanfossAlarm 10 / 11VLT FC 302 / FC 202

Thermal/Overload

Motor ETR / Thermistor Overtemp

Common Plant Causes
Motor running hot from continuous overload, blocked cooling fins, or open/tripped PTC thermistor in winding.
Multimeter / Insulation Megger Check
Measure motor frame temp with IR thermometer; check PTC resistance (< 100 Ohm cold, > 3 kOhm hot) on thermistor input.
Spare Part / Fix Required
Motor cooling fan cowl, PTC thermistor relay, or forced-ventilation blower.
DanfossAlarm 4VLT FC 302 / FC 202

Earth/Phase Loss

Mains Phase Imbalance / Loss

Common Plant Causes
Missing mains input phase, blown fuse on one leg, or > 3% voltage imbalance between L1/L2/L3.
Multimeter / Insulation Megger Check
Measure L1-L2, L2-L3, L1-L3 RMS voltages at drive input; check upstream fuses and breaker poles.
Spare Part / Fix Required
Input fuse link, MCCB contact block, or 3-phase line reactor.
DanfossAlarm 68VLT FC 302

Control/STO

Safe Stop / STO Activated

Common Plant Causes
24 VDC removed from Terminal 37 (Safe Torque Off) via E-stop, guard switch, or broken control wire.
Multimeter / Insulation Megger Check
Measure 24 VDC between Terminal 37 and Terminal 20 (GND); verify safety PLC / relay output.
Spare Part / Fix Required
Safety relay, guard interlock switch, or 24 VDC control PSU.
DeltaocAMS300 / C2000 / VFD-E

Overcurrent

Overcurrent During Acceleration

Common Plant Causes
Accel ramp time too short for load inertia, motor shorted at startup, or excessive low-frequency torque boost.
Multimeter / Insulation Megger Check
Megger motor at 1000 VDC; check U/V/W resistance balance; inspect load for mechanical bind on start.
Spare Part / Fix Required
Motor cable/winding repair, or IGBT module if drive trips with motor disconnected.
DeltaocdMS300 / C2000 / VFD-E

Overcurrent

Overcurrent During Deceleration

Common Plant Causes
Decel time too short causing over-fluxing/current spike, or mechanical brake engaging before output shuts off.
Multimeter / Insulation Megger Check
Measure current during decel; verify external holding brake release/engage timing.
Spare Part / Fix Required
Brake resistor / chopper or mechanical brake contactor.
DeltaocnMS300 / C2000 / VFD-E

Overcurrent

Overcurrent at Constant Speed

Common Plant Causes
Sudden process jam/slug load, transient cable short from vibration, or failing Hall current sensor.
Multimeter / Insulation Megger Check
Inspect motor clamp-on amps for spikes; Megger cable while flexing conduit; test drive with no motor.
Spare Part / Fix Required
Hall current sensor, IGBT module, or jammed pump/conveyor parts.
DeltaovAMS300 / C2000 / VFD-E

DC Bus Voltage

DC Bus Overvoltage

Common Plant Causes
Regenerative energy pushing DC bus > 400 VDC (230 V) or > 800 VDC (460 V), or high incoming mains voltage.
Multimeter / Insulation Megger Check
Check mains RMS voltage; measure braking resistor Ohms between +1/B1 and B2.
Spare Part / Fix Required
Dynamic braking resistor, braking unit, or input AC reactor.
DeltaLvAMS300 / C2000 / VFD-E

DC Bus Voltage

Low DC Bus Voltage (Undervoltage)

Common Plant Causes
Mains brownout, missing phase, loose R/S/T terminal screw, or open soft-start charge resistor.
Multimeter / Insulation Megger Check
Measure R-S-T line voltages under start; inspect pre-charge relay click and DC bus voltage display.
Spare Part / Fix Required
Soft-charge resistor, relay, input fuse, or DC bus capacitors.
DeltaoH1MS300 / C2000 / VFD-E

Thermal/Overload

Heatsink Overheat

Common Plant Causes
Heatsink cooling fan seized, dust-packed fins, ambient > 50 deg C, or faulty thermal sensor.
Multimeter / Insulation Megger Check
Check heatsink fan spinning speed; clean heatsink tunnels with dry compressed air; verify thermistor connection.
Spare Part / Fix Required
Cooling fan replacement, cabinet air filter, or thermal sensor.
DeltaoLMS300 / C2000 / VFD-E

Thermal/Overload

Motor / Drive Overload

Common Plant Causes
Output current exceeds electronic thermal relay curve (150% for 60 s) from high friction or undersized motor.
Multimeter / Insulation Megger Check
Check motor phase currents with true-RMS clamp; compare to motor nameplate FLA and drive Pr.06-xx.
Spare Part / Fix Required
Mechanical bearing/belt service or upsizing motor/VFD.
DeltaGFFMS300 / C2000 / VFD-E

Earth/Phase Loss

Ground Fault

Common Plant Causes
Leakage current to PE > 50% of drive rated current due to grounded motor phase or wet cable.
Multimeter / Insulation Megger Check
Disconnect U/V/W; Megger motor and cable at 1000 VDC to earth; test VFD unloaded to rule out faulty CT.
Spare Part / Fix Required
Motor stator rewind, power cable replacement, or Hall CT board.
DeltaPHLMS300 / C2000

Earth/Phase Loss

Input Phase Loss

Common Plant Causes
Open phase on R/S/T input, excessive DC bus ripple from failing capacitors, or unbalanced utility supply.
Multimeter / Insulation Megger Check
Check 3-phase input voltage balance (< 2%); inspect DC bus capacitors for bulging/leakage.
Spare Part / Fix Required
Upstream fuse/contactor or DC bus electrolytic capacitor kit.
DeltaSTo / STL1MS300 / C2000

Control/STO

Safe Torque Off / Safety Open

Common Plant Causes
S1/S2 safety terminals open from E-stop circuit, or internal safety channel discrepancy (STL1/STL2).
Multimeter / Insulation Megger Check
Measure 24 VDC at S1 and S2 against DCM; verify jumper or dual-channel safety relay.
Spare Part / Fix Required
Safety relay, E-stop switch, or control terminal board.
SchneiderOCFAltivar ATV320 / ATV630 / ATV930

Overcurrent

Overcurrent

Common Plant Causes
Incorrect motor parameter config, too high inertia/load shock, short circuit, or blocked rotor.
Multimeter / Insulation Megger Check
Disconnect motor leads; Megger windings >= 100 MOhm; check phase Ohms; verify ramp and U/f settings.
Spare Part / Fix Required
IGBT power module, motor cable, or motor rewind.
SchneiderOSFAltivar ATV320 / ATV630 / ATV930

DC Bus Voltage

Mains / DC Bus Overvoltage

Common Plant Causes
Mains voltage too high or excessive regenerative energy during fast braking without braking resistor.
Multimeter / Insulation Megger Check
Measure L1-L2-L3 mains voltage; check braking resistor resistance across PA/+ and PB.
Spare Part / Fix Required
Dynamic braking resistor, braking unit, or line choke.
SchneiderUSFAltivar ATV320 / ATV630 / ATV930

DC Bus Voltage

Mains Undervoltage

Common Plant Causes
Supply voltage drop, transient dip, loose mains lug, or defective pre-charge circuit.
Multimeter / Insulation Megger Check
Verify 3-phase input voltage under load; inspect DC bus pre-charge contactor/resistor.
Spare Part / Fix Required
Pre-charge resistor, mains contactor, or input fuses.
SchneiderOHFAltivar ATV320 / ATV630 / ATV930

Thermal/Overload

Drive Overheating

Common Plant Causes
Drive internal thermal state > 100% due to clogged cooling fins, dead fan, or high switching frequency.
Multimeter / Insulation Megger Check
Verify internal fan airflow and drive thermal state monitor (tHd); clean heatsink ducts.
Spare Part / Fix Required
Altivar replacement cooling fan or enclosure ventilation fan.
SchneiderOLFAltivar ATV320 / ATV630 / ATV930

Thermal/Overload

Motor Overload

Common Plant Causes
Motor I2t thermal protection tripped from sustained overcurrent, mechanical bind, or low-speed cooling loss.
Multimeter / Insulation Megger Check
Measure motor phase amps vs nameplate FLA; verify mechanical shaft freedom and motor fan.
Spare Part / Fix Required
Mechanical repair, external motor cooling blower, or motor service.
SchneiderSCF1Altivar ATV320 / ATV630 / ATV930

Overcurrent

Motor Short Circuit

Common Plant Causes
Dead short at drive output (phase-to-phase or phase-to-ground) detected on IGBT turn-on.
Multimeter / Insulation Megger Check
Disconnect U/V/W cables; Megger motor + cable; diode-test VFD output terminals.
Spare Part / Fix Required
Motor power cable, motor stator, or Altivar power stage.
SchneiderOPF2Altivar ATV320 / ATV630 / ATV930

Earth/Phase Loss

Motor 3-Phase Output Loss

Common Plant Causes
Open motor contactor between VFD and motor, broken conductor, or loose U/V/W lug.
Multimeter / Insulation Megger Check
Check U-V, V-W, W-U continuity through any isolation switch or thermal overload relay to motor.
Spare Part / Fix Required
Motor isolator / output contactor auxiliary, terminal lug, or motor cable.
SchneiderSTOAltivar ATV320 / ATV630 / ATV930

Control/STO

Safe Torque Off Active

Common Plant Causes
STO safety input at 0 V (E-stop pressed, safety curtain tripped, or missing 24 V jumper).
Multimeter / Insulation Megger Check
Measure 24 VDC at STOA/STOB terminals relative to COM/0V.
Spare Part / Fix Required
Safety relay module, E-stop contact, or STO terminal plug.
YaskawaoCGA700 / A1000 / V1000

Overcurrent

Overcurrent

Common Plant Causes
Output current exceeded hardware trip level (~200% rated) from phase short, rapid load impact, or blown IGBT.
Multimeter / Insulation Megger Check
Disconnect motor leads; Megger windings >= 100 MOhm; diode-check IGBT bridge U/V/W to +1/- terminals.
Spare Part / Fix Required
IGBT module, gate drive board, motor cable, or motor rewind.
YaskawaovGA700 / A1000 / V1000

DC Bus Voltage

DC Bus Overvoltage

Common Plant Causes
DC bus exceeded ~410 V (200 V class) or ~820 V (400 V class) from regen decel, surge, or open braking resistor.
Multimeter / Insulation Megger Check
Monitor U1-07 DC bus voltage; check input RMS mains; ohm-test braking resistor on B1/B2.
Spare Part / Fix Required
Braking resistor, braking transistor, or input AC reactor.
YaskawaUv1GA700 / A1000 / V1000

DC Bus Voltage

DC Bus Undervoltage

Common Plant Causes
DC bus dropped below ~190 V (200 V) / ~380 V (400 V) from mains dip, missing phase, or failed soft-charge relay.
Multimeter / Insulation Megger Check
Measure R/S/T input voltage; listen for soft-charge relay pull-in; check DC bus cap ESR.
Spare Part / Fix Required
Soft-charge resistor/contactor, input fuse, or DC bus capacitors.
YaskawaGFGA700 / A1000 / V1000

Earth/Phase Loss

Ground Fault

Common Plant Causes
Ground leakage > 50% of drive rated output current caused by insulation failure or moisture ingress.
Multimeter / Insulation Megger Check
Disconnect motor leads; Megger cable and motor separately at 1000 VDC; inspect junction box.
Spare Part / Fix Required
Motor cable, stator insulation repair, or internal Hall current sensor.
YaskawaoH1GA700 / A1000 / V1000

Thermal/Overload

Heatsink Overheat

Common Plant Causes
Heatsink temperature exceeded 90-105 deg C due to dead cooling fan, clogged heatsink, or high ambient temp.
Multimeter / Insulation Megger Check
Check cooling fan operation and U4-08 heatsink temp; clean cooling fins and cabinet filters.
Spare Part / Fix Required
Yaskawa OEM cooling fan kit or panel filter / air conditioner.
YaskawaoL1 / oL2GA700 / A1000 / V1000

Thermal/Overload

Motor / Drive Overload

Common Plant Causes
Continuous operation above motor FLA (oL1) or VFD rating (oL2); wrong motor rated amps E2-01.
Multimeter / Insulation Megger Check
Verify clamp-on amps on U/V/W; confirm E2-01 matches motor nameplate; check mechanical drag.
Spare Part / Fix Required
Mechanical load service, motor cooling fan, or VFD upsizing.
YaskawaLFGA700 / A1000 / V1000

Earth/Phase Loss

Output Phase Loss

Common Plant Causes
Open circuit in one motor output phase, loose terminal, or corroded motor isolator contact.
Multimeter / Insulation Megger Check
Check phase-to-phase Ohms at VFD U/V/W terminals (with LOTO); check clamp-on current balance.
Spare Part / Fix Required
Motor cable termination, output disconnect switch, or motor stator.
YaskawaHbb / HbbFGA700 / A1000 / V1000

Control/STO

Safe Disable / STO Input Open

Common Plant Causes
Safe Disable hardware inputs H1/H2 open (normal safety stop) or single-channel fault (HbbF).
Multimeter / Insulation Megger Check
Check 24 VDC on H1 and H2 relative to HC; test safety relay dual contacts for simultaneous switching.
Spare Part / Fix Required
Safety relay, safety wiring, or terminal board.
Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

What should a technician check first before resetting an overcurrent VFD fault?

Never repeatedly reset an overcurrent trip (F0001, 2310, oC, OCF) under load. Disconnect the motor leads at the VFD output terminals (U, V, W) and perform a 500 V / 1000 V DC insulation resistance (Megger) test to ground (>= 100 MOhm healthy, < 5 MOhm indicates winding or cable breakdown) plus phase-to-phase resistance balance check (< 2% deviation) before powering the drive.

Why does a VFD trip on DC bus overvoltage during deceleration?

When a high-inertia fan, centrifuge, or conveyor decelerates faster than friction can absorb kinetic energy, the motor acts as a generator and pumps regenerative energy back into the VFD DC link capacitors. This pushes DC bus voltage above ~780-820 VDC (on 400-480 V drives). Fix it by increasing deceleration ramp time, enabling overvoltage stall prevention, or installing a braking chopper and dynamic braking resistor.

How do you test a VFD IGBT power module with a digital multimeter?

Lock out and tag out mains power, wait at least 10-15 minutes for DC bus capacitors to discharge below 30 VDC, and disconnect input/motor cables. Set the multimeter to Diode mode: test between +DC/-DC bus terminals and U/V/W output terminals in both polarities. Each freewheeling diode should read ~0.35-0.55 V forward and OL reverse; a dead short (0.00 V) or open in both directions confirms a blown IGBT module.

What causes an intermittent Earth Fault or Ground Fault alarm on a VFD?

Long shielded motor cables (> 50-100 m) create high capacitive charging current to ground at high IGBT carrier frequencies, while moisture in motor junction boxes, aged stator varnish, or conductive dust inside the drive heatsink also trip earth fault protection (2330, Alarm 14, GFF, GF). Lowering the PWM carrier frequency, adding a dV/dt output reactor, and meggering the cable isolated from the motor pinpoints the cause.