Complete ABB VFD fault code chart for ACS580, ACS880, ACS355 & ACS550 drives: 2310, 3210, 2330, STO 5091 fixes, Megger checks & motor FLA calculator.
Showing 10 of 10 ABB fault codes
| Fault Code | Drive Series | Fault / Alarm | Category | Common Plant Causes | Multimeter / Megger Check | Spare Part / Fix |
|---|---|---|---|---|---|---|
2310 / F0001 |
ACS580 / ACS880 / ACS550 | Overcurrent | Overcurrent | Short circuit in motor cable/winding, mechanical jam, overly aggressive acceleration ramp, or incorrect motor nameplate / ID run data. | Disconnect U/V/W from drive; Megger phases to PE at 1000 VDC (>= 100 MOhm); measure phase-to-phase Ohms (< 2% imbalance); check IGBT diode drop. | Motor power cable, IGBT power module, Hall-effect current transducer (CT), or motor rewinding. |
3210 / F0002 |
ACS580 / ACS880 / ACS550 | DC Bus Overvoltage | DC Bus Voltage | High-inertia load regenerating during fast decel, mains voltage surge (> 480 VAC +10%), or open/failed dynamic braking resistor. | Measure incoming L1-L2-L3 RMS voltage and DC bus VDC (normal ~540-680 VDC on 400-480 V mains); check braking resistor Ohmic value against drive manual. | Dynamic braking resistor, braking chopper IGBT, or input AC line reactor. |
3220 / F0003 |
ACS580 / ACS880 / ACS550 | DC Bus Undervoltage | DC Bus Voltage | Mains sag or momentary power dip, blown input fuse, loose breaker lug, or failed pre-charge resistor/contactor. | Measure L1-L2-L3 under load; inspect DC bus voltage on keypad; test input rectifier diodes and DC pre-charge contactor coil/resistor. | Semiconductor input fuses, pre-charge resistor, input rectifier bridge, or DC bus electrolytic capacitors. |
2330 / F0016 |
ACS580 / ACS880 / ACS550 | Earth / Ground Fault | Earth/Phase Loss | Insulation breakdown in motor or submerged cable, moisture in terminal box, or excessive cable capacitance at high switching frequency. | Isolate cable from motor; Megger cable alone and motor alone at 500/1000 VDC to PE; inspect motor junction box for condensation. | Motor terminal block/gland seal, armoured motor cable, dV/dt output choke, or current sensor board. |
4210 / F0004 |
ACS580 / ACS880 / ACS550 | IGBT / Drive Overtemperature | Thermal/Overload | Clogged panel air filters, failed internal heatsink cooling fan, ambient > 40-50 deg C, or excessive carrier frequency. | Check heatsink fan rotation and 24 VDC supply; inspect cabinet intake louvers and heatsink fins; read IGBT temp parameter in diagnostics. | Internal heatsink cooling fan, panel filter mats, cabinet exhaust fan, or thermal paste / NTC sensor. |
7121 |
ACS580 / ACS880 | Motor Stall | Thermal/Overload | Mechanical rotor lock, seized pump/gearbox bearing, belt jam, or V/Hz torque boost too low at low speed. | Spin driven shaft manually (LOTO); measure motor phase amps with true-RMS clamp meter; verify gearbox oil and coupling. | Driven equipment bearings, coupling insert, or drive current-limit / stall supervision tuning. |
STO / 5091 |
ACS580 / ACS880 | Safe Torque Off Active | Control/STO | Safety relay/E-stop loop open, loose 24 VDC jumper on XSTO terminals, or single-channel discrepancy between STO1 and STO2. | Measure 24 VDC on both STO1 and STO2 inputs relative to 0 V / SGND; verify E-stop mushroom button and safety relay contacts. | Dual-channel safety relay, E-stop contact block, or XSTO plug connector. |
3130 |
ACS580 / ACS880 | Input Phase Loss | Earth/Phase Loss | Blown upstream HRC fuse, tripped single-phase contactor contact, severe mains voltage unbalance (> 3%), or loose terminal lug. | Measure L1-L2, L2-L3, L1-L3 line voltages at drive input terminals with multimeter; check thermal discoloration on lugs. | Upstream HRC/gG input fuse, mains contactor contact kit, or input rectifier diode module. |
2340 |
ACS580 / ACS880 | Output Short Circuit | Overcurrent | Dead short phase-to-phase in motor winding or junction box, or shorted output IGBT leg. | Isolate U/V/W leads; measure phase-to-phase resistance (should be symmetric); test U/V/W to +DC/-DC diodes on VFD. | IGBT power module, gate driver board, or motor stator rewind / cable replacement. |
5081 |
ACS580 / ACS880 | Auxiliary Fan Fault | Thermal/Overload | Stalled cooling fan bearing, dust-jammed fan impeller, or broken fan tachometer feedback wire. | Check 24 VDC at fan connector; spin fan blades by hand for bearing drag; inspect tach wire continuity. | OEM VFD cooling fan kit (heatsink / control-board fan). |
No matching rows found. Clear the search box or switch back to All.
ABB Field Diagnostic Protocol (LOTO, Megger & IGBT Test)
- Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
- Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the ABB output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
- Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
- IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Electric Motor FLA, Starter & Overload Sizing Calculator
Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Frequently Asked Questions
How do I fix ABB VFD fault 2310 or F0001 Overcurrent on ACS580 / ACS880?
Disconnect U/V/W motor cables at the drive output, perform a 1000 VDC Megger insulation test on motor and cable (>= 100 MOhm healthy), verify phase-to-phase Ohms (< 2% imbalance), and check for mechanical shaft jam or too-short acceleration ramp (Par 23.12).
What does ABB fault 2330 Earth Fault mean and how do I isolate it?
ABB 2330 indicates ground leakage current above trip threshold. Isolate the motor cable from the motor terminal box and Megger the cable and stator separately at 1000 VDC. Long shielded cables (> 75 m) may also require lowering switching frequency or adding a dV/dt output choke.
Why is ABB ACS580 showing STO 5091 Safe Torque Off?
STO 5091 means the 24 VDC safety loop on XSTO terminals (IN1/IN2) is open. Check E-stop mushroom buttons, dual-channel safety relay outputs, and loose XSTO connector plugs with a multimeter relative to SGND.