Schneider Altivar VFD Fault Codes (ATV320, ATV630): Diagnostic Chart

Schneider Electric Altivar ATV320, ATV630 & ATV930 fault troubleshooting guide: OCF, OSF, USF, OHF, OLF, SCF1, OPF2 & STO checks with spare parts.

Showing 8 of 8 Schneider fault codes

Fault Code Drive Series Fault / Alarm Category Common Plant Causes Multimeter / Megger Check Spare Part / Fix
OCF Altivar ATV320 / ATV630 / ATV930 Overcurrent Overcurrent Incorrect motor parameter config, too high inertia/load shock, short circuit, or blocked rotor. Disconnect motor leads; Megger windings >= 100 MOhm; check phase Ohms; verify ramp and U/f settings. IGBT power module, motor cable, or motor rewind.
OSF Altivar ATV320 / ATV630 / ATV930 Mains / DC Bus Overvoltage DC Bus Voltage Mains voltage too high or excessive regenerative energy during fast braking without braking resistor. Measure L1-L2-L3 mains voltage; check braking resistor resistance across PA/+ and PB. Dynamic braking resistor, braking unit, or line choke.
USF Altivar ATV320 / ATV630 / ATV930 Mains Undervoltage DC Bus Voltage Supply voltage drop, transient dip, loose mains lug, or defective pre-charge circuit. Verify 3-phase input voltage under load; inspect DC bus pre-charge contactor/resistor. Pre-charge resistor, mains contactor, or input fuses.
OHF Altivar ATV320 / ATV630 / ATV930 Drive Overheating Thermal/Overload Drive internal thermal state > 100% due to clogged cooling fins, dead fan, or high switching frequency. Verify internal fan airflow and drive thermal state monitor (tHd); clean heatsink ducts. Altivar replacement cooling fan or enclosure ventilation fan.
OLF Altivar ATV320 / ATV630 / ATV930 Motor Overload Thermal/Overload Motor I2t thermal protection tripped from sustained overcurrent, mechanical bind, or low-speed cooling loss. Measure motor phase amps vs nameplate FLA; verify mechanical shaft freedom and motor fan. Mechanical repair, external motor cooling blower, or motor service.
SCF1 Altivar ATV320 / ATV630 / ATV930 Motor Short Circuit Overcurrent Dead short at drive output (phase-to-phase or phase-to-ground) detected on IGBT turn-on. Disconnect U/V/W cables; Megger motor + cable; diode-test VFD output terminals. Motor power cable, motor stator, or Altivar power stage.
OPF2 Altivar ATV320 / ATV630 / ATV930 Motor 3-Phase Output Loss Earth/Phase Loss Open motor contactor between VFD and motor, broken conductor, or loose U/V/W lug. Check U-V, V-W, W-U continuity through any isolation switch or thermal overload relay to motor. Motor isolator / output contactor auxiliary, terminal lug, or motor cable.
STO Altivar ATV320 / ATV630 / ATV930 Safe Torque Off Active Control/STO STO safety input at 0 V (E-stop pressed, safety curtain tripped, or missing 24 V jumper). Measure 24 VDC at STOA/STOB terminals relative to COM/0V. Safety relay module, E-stop contact, or STO terminal plug.

Schneider Field Diagnostic Protocol (LOTO, Megger & IGBT Test)

  1. Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
  2. Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Schneider output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
  3. Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
  4. IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Live Interactive Calculator · SI Metric & US Imperial

Electric Motor FLA, Starter & Overload Sizing Calculator

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

V

cos φ

%


Results

Full-load current (FLA)
—
A

Starting peak current
—
A

Overload relay setting (1.05× FLA)
—
A

Min. AC-3 contactor rating (1.25× FLA)
—
A

Input apparent power
—
kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

How do I fix Schneider Altivar SCF1 Motor Short Circuit vs OCF Overcurrent?

SCF1 indicates an instantaneous phase-to-phase or phase-to-ground short detected at IGBT turn-on (test U/V/W Megger and IGBT diode bridge). OCF is sustained overcurrent from overload, wrong motor tuning, or inertia shock.

What causes Schneider OPF2 Motor 3-Phase Output Loss?

OPF2 trips when the output contactor between the Altivar drive and motor is open, a motor power lug is loose, or one stator phase is open-circuited.

Why does ATV630 / ATV320 trip on OSF Overvoltage?

OSF occurs when DC bus voltage exceeds limit due to regenerative braking from a high-inertia load or incoming mains surge. Extend decel ramp (dEC) or fit a braking resistor on PA/+ and PB.