Schneider Electric Altivar ATV320, ATV630 & ATV930 fault troubleshooting guide: OCF, OSF, USF, OHF, OLF, SCF1, OPF2 & STO checks with spare parts.
Showing 8 of 8 Schneider fault codes
| Fault Code | Drive Series | Fault / Alarm | Category | Common Plant Causes | Multimeter / Megger Check | Spare Part / Fix |
|---|---|---|---|---|---|---|
OCF |
Altivar ATV320 / ATV630 / ATV930 | Overcurrent | Overcurrent | Incorrect motor parameter config, too high inertia/load shock, short circuit, or blocked rotor. | Disconnect motor leads; Megger windings >= 100 MOhm; check phase Ohms; verify ramp and U/f settings. | IGBT power module, motor cable, or motor rewind. |
OSF |
Altivar ATV320 / ATV630 / ATV930 | Mains / DC Bus Overvoltage | DC Bus Voltage | Mains voltage too high or excessive regenerative energy during fast braking without braking resistor. | Measure L1-L2-L3 mains voltage; check braking resistor resistance across PA/+ and PB. | Dynamic braking resistor, braking unit, or line choke. |
USF |
Altivar ATV320 / ATV630 / ATV930 | Mains Undervoltage | DC Bus Voltage | Supply voltage drop, transient dip, loose mains lug, or defective pre-charge circuit. | Verify 3-phase input voltage under load; inspect DC bus pre-charge contactor/resistor. | Pre-charge resistor, mains contactor, or input fuses. |
OHF |
Altivar ATV320 / ATV630 / ATV930 | Drive Overheating | Thermal/Overload | Drive internal thermal state > 100% due to clogged cooling fins, dead fan, or high switching frequency. | Verify internal fan airflow and drive thermal state monitor (tHd); clean heatsink ducts. | Altivar replacement cooling fan or enclosure ventilation fan. |
OLF |
Altivar ATV320 / ATV630 / ATV930 | Motor Overload | Thermal/Overload | Motor I2t thermal protection tripped from sustained overcurrent, mechanical bind, or low-speed cooling loss. | Measure motor phase amps vs nameplate FLA; verify mechanical shaft freedom and motor fan. | Mechanical repair, external motor cooling blower, or motor service. |
SCF1 |
Altivar ATV320 / ATV630 / ATV930 | Motor Short Circuit | Overcurrent | Dead short at drive output (phase-to-phase or phase-to-ground) detected on IGBT turn-on. | Disconnect U/V/W cables; Megger motor + cable; diode-test VFD output terminals. | Motor power cable, motor stator, or Altivar power stage. |
OPF2 |
Altivar ATV320 / ATV630 / ATV930 | Motor 3-Phase Output Loss | Earth/Phase Loss | Open motor contactor between VFD and motor, broken conductor, or loose U/V/W lug. | Check U-V, V-W, W-U continuity through any isolation switch or thermal overload relay to motor. | Motor isolator / output contactor auxiliary, terminal lug, or motor cable. |
STO |
Altivar ATV320 / ATV630 / ATV930 | Safe Torque Off Active | Control/STO | STO safety input at 0 V (E-stop pressed, safety curtain tripped, or missing 24 V jumper). | Measure 24 VDC at STOA/STOB terminals relative to COM/0V. | Safety relay module, E-stop contact, or STO terminal plug. |
No matching rows found. Clear the search box or switch back to All.
Schneider Field Diagnostic Protocol (LOTO, Megger & IGBT Test)
- Lockout / Tagout & DC Bus Discharge: Isolate incoming 3-phase mains and wait 10–15 minutes until DC bus voltage across +DC/-DC measures below 30 VDC with a CAT III/IV multimeter.
- Motor & Cable Megger Test (1000 VDC): Disconnect U, V, W motor leads from the Schneider output terminals. Test each phase to earth (PE) at 500–1000 VDC (≥ 100 MΩ healthy; < 5 MΩ means wet/damaged winding or cable).
- Stator Phase Balance: Measure phase-to-phase resistance (U-V, V-W, W-U) at the disconnected leads; imbalance > 2% indicates a shorted turn or loose crimp lug.
- IGBT Bridge Diode Check: With motor leads off and multimeter in Diode mode, test U/V/W to +DC and -DC in both polarities (~0.35–0.55 V forward, OL reverse). A 0.00 V short confirms a failed IGBT module.
Electric Motor FLA, Starter & Overload Sizing Calculator
Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Frequently Asked Questions
How do I fix Schneider Altivar SCF1 Motor Short Circuit vs OCF Overcurrent?
SCF1 indicates an instantaneous phase-to-phase or phase-to-ground short detected at IGBT turn-on (test U/V/W Megger and IGBT diode bridge). OCF is sustained overcurrent from overload, wrong motor tuning, or inertia shock.
What causes Schneider OPF2 Motor 3-Phase Output Loss?
OPF2 trips when the output contactor between the Altivar drive and motor is open, a motor power lug is loose, or one stator phase is open-circuited.
Why does ATV630 / ATV320 trip on OSF Overvoltage?
OSF occurs when DC bus voltage exceeds limit due to regenerative braking from a high-inertia load or incoming mains surge. Extend decel ramp (dEC) or fit a braking resistor on PA/+ and PB.