Yaskawa V1000, A1000, and GA700 oC, GF, ov, and oL2 Fault Troubleshooting

Fix Yaskawa V1000, A1000, and GA700 oC, GF, ov, and oL2 trips fast. Inspect U2-01..U2-07 fault traces, L3-04 decel stall, C6-02 carrier, and E2-01 FLA.

Jignesh S Panchal 8 min read
Predictive Maintenance: A starter guide for plants (cover graphic)
Approx. 9 min read
On this page
  1. Immediate Yaskawa V1000, A1000, and GA700 oC, GF, ov, and oL2 Triage
  2. Reading U2-01 Through U2-07 Fault Trace Monitors Before Reset
  3. Yaskawa V1000, A1000, and GA700 Fault Matrix: oC, GF, ov, oL2, and Uv1
  4. Tuning C1-01, C1-02, L3-04, C6-02, and E2-01 to Clear Repeat Trips
  5. Bench Isolation for GF Leakage and Hardware oC Trips
  6. Frequently Asked Questions
  7. What DC bus voltage trips ov on a Yaskawa V1000, A1000, or GA700?
  8. How is Yaskawa oL2 different from oL1?
  9. Why does Yaskawa GF trigger on a brand-new motor with >500 M-ohm insulation?
  10. Which U2 fault trace parameter proves whether oC happened during startup or braking?
  11. More on Motors, Drives and Electrical

Immediate Yaskawa V1000, A1000, and GA700 oC, GF, ov, and oL2 Triage

Read fault trace monitors U2-01 through U2-07 before pressing RESET on a tripped Yaskawa V1000, A1000, or GA700. Hardware overcurrent oC triggers near 200% of rated heavy-duty drive current, while ground fault GF fires once output earth leakage crosses 50% of rated current. Overvoltage ov latches at roughly 820 V DC on 400 V class drives (410 V DC on 200 V class models). Lock out incoming AC mains for 5 minutes until DC bus voltage across +1/+3 and – bleeds under 50 V DC, unbolt leads U/T1, V/T2, and W/T3, and megger motor windings at 1,000 V DC (>100 M-ohm to frame). Audit C1-01 accel, C1-02 decel, L3-04 decel stall prevention, C6-02 carrier frequency (2-15 kHz), and E2-01 motor FLA before restoring load.

Never mash reset blindly. Restarting a Yaskawa A1000 or GA700 repeatedly into a dead Phase W cable short cooks the IGBT brick in under 10 ms and wipes out the gate-drive circuit. Compare auxiliary drive alarms inside our Yaskawa VFD fault codes troubleshooting guide or run cross-brand fault checks in the VFD fault code troubleshooter.

Reading U2-01 Through U2-07 Fault Trace Monitors Before Reset

Yaskawa drives freeze a complete electrical snapshot inside monitor group U2 at the exact millisecond a fault opens the output bridge. Skipping those eight numbers wastes hours chasing phantom parameter bugs when the keypad already captured output amps, frequency, and bus voltage at trip time. Walk through U2-01 through U2-08 in sequence before touching a screwdriver.

Advertisement
  • U2-01 (Current Fault) and U2-02 (Previous Fault): Confirm whether oC, GF, ov, or oL2 is an isolated event or part of a repeating sequence preceded by Uv1 line dips.
  • U2-03 (Frequency Reference at Fault) vs U2-04 (Output Frequency at Fault): Compare commanded speed against actual shaft frequency at the trip instant. When U2-03 sits at 50.0 Hz while U2-04 reads 4.2 Hz, the fault struck during early acceleration; when U2-03 reads 0.0 Hz while U2-04 sits at 36.5 Hz, regenerative deceleration triggered the trip.
  • U2-05 (Output Current at Fault): Check peak amps directly against drive rated current and E2-01 motor FLA to separate hard phase shorts from gradual mechanical binding.
  • U2-06 (Motor Speed at Fault) and U2-07 (Output Voltage Reference at Fault): Flag open-loop slip runaway or collapsed V/f voltage curves under heavy startup torque, and check U2-08 right afterward to verify whether DC bus voltage crossed 820 V DC (400 V class) or sagged below 380 V DC.

Operators ruin this diagnostic goldmine constantly. Hitting RESET and pressing RUN three times before calling maintenance pushes the original Uv1 or ov root trigger out of U2-01 and U2-02, replacing the real plant disturbance with secondary restart oC faults that send technicians down the wrong path for half a shift. Train operators to photograph U2-01 through U2-08 on their phone before clearing any trip.

Yaskawa V1000, A1000, and GA700 Fault Matrix: oC, GF, ov, oL2, and Uv1

Yaskawa firmware draws sharp lines between instantaneous hardware overcurrent, ground leakage, regenerative DC surges, sustained inverter thermal overload, and input power loss across five core fault codes. Match the keypad code against its exact threshold and immediate field verification step.

Fault Code Fault Name Trip Threshold Primary Shop-Floor Trigger Immediate Diagnostic Check
oC Overcurrent Output current exceeds ~200% rated heavy-duty drive current Phase-to-phase short, seized shaft, short C1-01 ramp, or failed IGBT leg Inspect U2-04/U2-05, disconnect U/V/W, check <2% winding balance, extend C1-01.
GF Ground fault Output earth leakage exceeds ~50% of drive rated output current Wet stator insulation, pinched cable to conduit, long cable + high C6-02 kHz Lock out 5 min, disconnect U/V/W, megger at 1,000 V DC (>100 M-ohm), lower C6-02.
ov DC bus overvoltage DC bus reaches ~820 V DC (400 V class) or ~410 V DC (200 V class) Fast C1-02 decel on high inertia, wrong L3-04 setting, or open brake resistor Read U2-08 bus volts, extend C1-02, check L3-04 and B1/B2 brake resistor ohms.
oL2 Drive overload Electronic thermal curve exceeded (150% HD / 120% ND for 60 s) Heavy load, wrong C6-01 duty mode, high C6-02 derating, or plugged cooling fins Audit U2-05 vs drive rating, drop C6-02 to 2-5 kHz, verify mechanical drag.
Uv1 DC bus undervoltage DC bus drops below ~380 V DC (400 V class) or ~190 V DC (200 V class) Line voltage sag, blown input fuse, loose R/L1-S/L2-T/L3 lug, bad pre-charge relay Measure all three AC supply phases under load and tighten input power terminals.

Tuning C1-01, C1-02, L3-04, C6-02, and E2-01 to Clear Repeat Trips

Verified motor copper and clean bearings mean software settings are fighting load physics. Step through these five Yaskawa parameters across V1000, A1000, and GA700 controllers before replacing power hardware.

  • C1-01 (Acceleration Time 1): Increase C1-01 from factory 10 s up to 20-35 s on loaded crushers, heavy screw conveyors, and large centrifugal fans. Tight 3 s to 5 s ramps demand breakaway torque well past 180% FLA, hammering right into oC or building rapid oL2 thermal accumulation on repeated cycle starts.
  • C1-02 (Deceleration Time 1): Extend C1-02 to 20-60 s on high-inertia blowers, centrifuges, and hammer mills so kinetic energy dissipates smoothly without pushing DC bus voltage from 565 V DC (400 V grid) or 650 V DC (460 V grid) up past the 820 V DC ov trip point.
  • L3-04 (Stall Prevention Selection During Deceleration): Choose L3-04 = 1 (General Purpose) whenever no braking resistor is fitted so the drive stretches deceleration automatically as DC bus voltage rises. Switch L3-04 = 0 (Disabled) when an external braking resistor connects to terminals B1 and B2, or select L3-04 = 3 (General Purpose with Braking Resistor) on A1000 and GA700 panels needing maximum stopping repeatability. Leaving L3-04 = 0 with zero braking resistor guarantees ov on every rapid stop.
  • C6-02 (Carrier Frequency Selection, 2-15 kHz): High PWM carrier frequencies quiet motor whine at a brutal thermal price. Cranking C6-02 from 2 kHz (setting 1) or 5 kHz (setting 2) up to 10 kHz (setting 4) or 15 kHz (setting 6) forces up to 20% to 40% inverter output current derating that pushes marginal frames straight into oL2, while pumping capacitive leakage into shielded cables >50 m until GF fires. Drop C6-02 back to 2 kHz or 5 kHz first.
  • E2-01 (Motor Rated Current / FLA): Enter the exact physical nameplate amperage into E2-01 and cross-check expected full-load amps using the electric motor FLA and starter calculator. Wrong E2-01 entries distort vector flux limits and mask the real split between oL1 (motor thermal overload) and oL2 (inverter hardware overload).

Watch the Normal Duty vs Heavy Duty trap inside C6-01. A Yaskawa GA700 or A1000 rated 18.5 kW at Normal Duty (120% for 60 s) delivers only 15 kW at Heavy Duty (150% for 60 s). Running an 18.5 kW constant-torque conveyor on that borderline frame trips oL2 like clockwork every afternoon once enclosure ambient crosses 40 C. No parameter tweak rescues an undersized inverter pulling 112% current around the clock.

Bench Isolation for GF Leakage and Hardware oC Trips

Lock out incoming three-phase mains and verify zero voltage across R/L1, S/L2, and T/L3 before opening the power cover. Wait at least 5 minutes (up to 10 minutes on 75 kW+ A1000/GA700 frames) until the CHARGE LED goes completely dark and a CAT III meter reads below 50 V DC across DC bus terminals +1/+3 and -.

Unbolt motor leads U/T1, V/T2, and W/T3 at the drive AND isolate the motor junction box if cable length exceeds 20 m. Megger each stator winding to ground at 1,000 V DC for 60 seconds: healthy dry 400 V or 480 V motors exceed 100 M-ohm, standalone feeder cables hold above 50 M-ohm, and anything below 5 M-ohm indicates moisture tracking or carbonized slot insulation. Follow up with a four-wire milliohmmeter across U-V, V-W, and W-U, where phase resistance deviation above 2% catches inter-turn winding shorts that trip oC at 200% peak current.

Advertisement

Test the disconnected Yaskawa power bridge last. Switch a digital multimeter to diode check across terminals U/T1, V/T2, and W/T3 against both DC bus positive (+1/+3) and DC bus negative (-). Healthy IGBT freewheeling diodes show a uniform 0.35 V to 0.55 V forward drop in one polarity and open circuit when leads reverse. A 0.00 V reading proves blown silicon immediately.

Frequently Asked Questions

What DC bus voltage trips ov on a Yaskawa V1000, A1000, or GA700?

Overvoltage fault ov trips at roughly 820 V DC on 400 V class drives and roughly 410 V DC on 200 V class models. Inspect U2-08 right after a trip, lengthen C1-02 deceleration time, verify L3-04 matches whether a braking resistor is wired to B1/B2, and check incoming AC line voltage for swells exceeding +10%.

How is Yaskawa oL2 different from oL1?

Fault oL1 protects the motor windings based on nameplate current entered in E2-01, whereas oL2 protects the drive IGBTs when output current stays past the inverter thermal curve (150% HD or 120% ND for 60 s). Fix recurring oL2 trips by lowering C6-02 carrier frequency toward 2-5 kHz, extending C1-01 accel time, cleaning heatsink fins, or checking mechanical overload.

Why does Yaskawa GF trigger on a brand-new motor with >500 M-ohm insulation?

Long shielded motor cables exceeding 50 m paired with a high C6-02 carrier frequency (8-15 kHz) create high-frequency capacitive earth leakage that crosses the 50% GF threshold during PWM switching. Drop C6-02 to 2 kHz (setting 1), verify output grounding continuity, and install an output dV/dt reactor on runs past 100 m.

Which U2 fault trace parameter proves whether oC happened during startup or braking?

Compare U2-03 (Frequency Reference at Fault) against U2-04 (Output Frequency at Fault) alongside U2-05 (Output Current at Fault). Higher U2-03 than U2-04 confirms an acceleration trip pointing toward C1-01, breakaway friction, or motor shorts, whereas lower U2-03 than U2-04 points toward deceleration regen or mechanical load shock.

Free tool for this topic

Electric Motor FLA, Starter & Overload Sizing CalculatorCalculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Open calculator

Continue learning

More on Motors, Drives and Electrical

View all →
Sponsored
Jignesh S Panchal
Technical Editorial Author Verified Editor

Jignesh S Panchal

Founder — Jaadu Digital & Musafir Infotech · 9+ Years in Industrial B2B

Jignesh S Panchal is the founder of Jaadu Digital and Musafir Infotech, and the publisher behind EngiTech. With over 9 years of hands-on experience in industrial marketing and B2B growth, he works closely with machinery OEMs, process equipment manufacturers, and industrial service providers across thermal processing, fluid handling, automation, packaging, and plant reliability. Combining deep practical knowledge of industrial manufacturing with how technical buyers actually evaluate equipment, he built EngiTech to give plant engineers and procurement teams reliable sizing tools, fault diagnostics, and verified B2B supplier discovery.