New in the library Presented by Jaadu Digital ↗
Free Business Profile Free tools
Motors, Drives and Electrical

Schneider Altivar ATV320 and ATV630 OCF, SCF1, and OBF Fault Troubleshooting

Solve Schneider Altivar ATV320 and ATV630 OCF, SCF1, SCF3, and OBF faults. Tune ACC, DEC, brA, and tUn, test 820 V DC bus trips, and size brake resistors.

Jignesh S Panchal 7 min read
Predictive Maintenance: A starter guide for plants (cover graphic)
Approx. 8 min read
On this page
  1. Immediate Schneider Altivar ATV320 and ATV630 OCF, SCF1, and OBF Checklist
  2. Troubleshooting Matrix: Altivar OCF, SCF1, SCF3, and OBF Faults
  3. Solving OCF and SCF1: ACC Ramps, Mechanical Drag, and Cold tUn Auto-Tuning
  4. Fixing OBF Overbraking: 820 V DC Bus Physics, DEC, and brA Adaptation
  5. Braking Resistor Ohmic Minimum Check Between PA/+ and PB
  6. Frequently Asked Questions
  7. What DC bus voltage triggers an OBF fault on a 400 V Schneider Altivar drive?
  8. Should brA be set to YES or NO when using an external braking resistor?
  9. How do I tell SCF1 and SCF3 apart on an Altivar ATV320 or ATV630?
  10. Why does my Altivar drive trip on OCF right after running tUn auto-tuning?
  11. More on Motors, Drives and Electrical

Immediate Schneider Altivar ATV320 and ATV630 OCF, SCF1, and OBF Checklist

Isolate electrical shorts from mechanical overload before resetting a Schneider Electric Altivar ATV320 or ATV630 tripped on OCF (Overcurrent), SCF1 (Motor short circuit), SCF3 (Ground short circuit), or OBF (Overbraking). On 400 V AC three-phase Altivar drives, resting DC bus voltage sits near 565 V DC, internal braking choppers fire around 780 V to 790 V DC, and OBF trips at roughly 820 V DC whenever fast deceleration dumps excess regenerative energy back into the DC capacitors. For OCF and SCF1/SCF3 faults, lock out mains power for 15 minutes until DC bus voltage drops below 50 V DC, disconnect motor cables from terminals U/T1, V/T2, and W/T3, and megger windings at 1,000 V DC (above 100 M-ohm to earth). For OBF trips, check incoming line voltage, extend deceleration ramp DEC, verify deceleration ramp adaptation brA, and measure external braking resistor ohms against the frame minimum rating between PA/+ and PB.

Stop hammering reset on SCF1. Re-enabling an Altivar inverter into a dead phase-to-phase cable short vaporizes the output IGBT module in under 5 ms. Cross-reference every sub-fault menu in our Schneider Altivar VFD fault codes troubleshooting guide or run structured isolation steps inside the VFD fault code troubleshooter.

Troubleshooting Matrix: Altivar OCF, SCF1, SCF3, and OBF Faults

Schneider Altivar ATV320 and ATV630 firmware separates acceleration overcurrent, phase-to-phase shorts, ground leakage, and regenerative DC overvoltage across four clear trip codes. Match the code before touching wiring.

Advertisement
Altivar Fault Fault Description Trigger Threshold / Mechanism Primary Shop-Floor Causes First Field Action
OCF Overcurrent Output current exceeds hardware/software limit (~180% to 220% peak) Short ACC ramp, seized bearing, wrong motor data, or stale tUn auto-tune Spin load shaft by hand, verify nPr/UnS/nCr nameplate data, and lengthen ACC.
SCF1 Motor short circuit Instantaneous phase-to-phase overcurrent at U/T1, V/T2, W/T3 Shorted motor cable, burnt stator turns, or low-inductance mismatch after failed tUn Lock out power, disconnect motor leads, test phase ohms (<2% balance), and check IGBTs.
SCF3 Ground short circuit Phase-to-earth leakage or direct short on drive output stage Water in terminal box, pinched conduit wire, or high SFr switching on >50 m cable Megger motor (>100 M-ohm) and cable (>50 M-ohm) at 1,000 V DC, and lower SFr to 4 kHz.
OBF Overbraking (DC bus high) DC bus voltage crosses ~820 V DC on 400 V class drives Fast DEC ramp on high inertia, high mains >440 V AC, open brake resistor, or brA off Check mains voltage, extend DEC, verify brA mode, and ohm-test PA/+ to PB resistor.

Solving OCF and SCF1: ACC Ramps, Mechanical Drag, and Cold tUn Auto-Tuning

Mechanical binding masquerades as an electrical OCF fault on conveyors, mixers, and shredders constantly. A dry or spalled gearbox bearing spikes breakaway torque right at 1.5 Hz and trips OCF in 2 seconds, looking identical to a tight acceleration ramp until a technician uncouples the motor and tries turning the driven shaft by hand. If you replace bearings repeatedly on high-load shafts, check rated radial load and service hours in our bearing life L10 number calculator so mechanical drag does not keep cooking VFD power stages.

After confirming free mechanical rotation and clean 1,000 V DC insulation resistance, audit motor parameters and ramps in the Altivar menu:

  • ACC (Acceleration Ramp Time): Lengthen ACC from factory 3.0 s to 10.0-20.0 s on high-inertia centrifugal fans, heavy belts, or positive-displacement pumps where startup inertia pulls high breakaway amps.
  • Nameplate Parameters (nPr, UnS, nCr, FrS, nSP): Verify rated power (nPr), rated voltage (UnS = 400 V), rated current (nCr), rated frequency (FrS = 50 Hz), and nominal speed (nSP) directly off the physical motor plate before tuning. Confirm physical terminal links match Delta or Star for 400 V mains.
  • tUn (Auto-Tuning): Run tUn at standstill on a cold motor (ambient 20 °C) whenever installing a new motor, changing cable lengths, or recovering from false OCF/SCF1 trips. Executing tUn right after a four-hour production run at 95 °C bakes elevated hot stator resistance (+25% above cold copper) into the ATV630 flux estimator, guaranteeing cold-start OCF trips every Monday morning.
  • SFr (Switching Frequency for SCF3): Drop SFr from 8 kHz, 12 kHz, or 16 kHz down to 4 kHz on shielded motor cables longer than 50 m. High switching frequencies drive capacitive charging spikes into cable armor that trip SCF3 earth fault protection even when insulation tests clean.

Fixing OBF Overbraking: 820 V DC Bus Physics, DEC, and brA Adaptation

Overbraking trips happen when kinetic energy from a spinning rotor turns the induction motor into a generator, pumping current backward through the IGBT freewheeling diodes into the DC link capacitors. On a nominal 400 V AC supply, resting DC bus voltage reads 565 V DC (400 V x 1.414), leaving roughly 255 V of storage margin before OBF fires around 820 V DC. Check incoming plant mains immediately if OBF strikes during mild speed changes: a facility transformer tapped hot at 440 V AC pushes idle DC bus voltage up to 622 V DC, stripping away 57 V of braking margin before deceleration even starts.

Tune DEC and brA together to match your exact load duty:

  • DEC (Deceleration Ramp Time): Extend DEC from 3 s to 15-30 s on high-inertia exhaust fans, centrifuges, and long roller conveyors where rapid stopping is unnecessary. Doubling deceleration time cuts regenerative power flowing back into the DC bus in half.
  • brA (Deceleration Ramp Adaptation): Set brA to YES on non-positioning loads without a braking resistor (such as HVAC fans and centrifugal pumps) so the ATV320 or ATV630 automatically stretches DEC whenever DC bus voltage climbs toward 780 V DC. Switch brA to NO the moment you wire an external braking resistor bank! Leaving brA set to YES alongside a newly installed braking resistor forces the drive to stretch stop time before the braking chopper ever turns on, leaving the resistor stone-cold while operators assume the braking transistor is dead.

Braking Resistor Ohmic Minimum Check Between PA/+ and PB

Installing an undersized ohmic braking resistor destroys Altivar braking choppers on the very first hard stop. Every ATV320 and ATV630 power frame specifies a hard minimum braking resistance (R_min) between DC bus terminal PA/+ and chopper terminal PB, ranging from roughly 28 ohm to 60 ohm on 2.2 kW to 7.5 kW ATV320 units down to 5 ohm to 15 ohm on 15 kW to 37 kW frames. Calculate peak transistor current as I_chop = V_chop / R_brake: landing a 10-ohm resistor across a 785 V DC braking chopper pulls 78.5 A straight through a 30 A internal IGBT switch and blows the module instantly.

Check the opposite failure mode whenever an existing resistor system suddenly starts logging OBF. Lock out power, verify DC bus falls below 50 V DC across PA/+ and PC/-, disconnect one resistor lead, and measure resistance directly across the external resistor bank. An open circuit (infinite ohms) traces to a burnt wirewound element, melted terminal block, or tripped external thermal overload relay mounted on the resistor enclosure; a dead zero-ohm short across PA/+ and PB confirms either a pinched wire or a shorted internal braking transistor requiring drive repair.

Advertisement

Frequently Asked Questions

What DC bus voltage triggers an OBF fault on a 400 V Schneider Altivar drive?

Altivar 400 V drives trip OBF near 820 V DC. Resting DC bus voltage sits around 565 V DC on a nominal 400 V three-phase line, while high incoming plant mains above 435 V AC push idle bus voltage past 615 V DC and shrink deceleration headroom sharply.

Should brA be set to YES or NO when using an external braking resistor?

Set brA to NO for braking resistors. Leaving brA (Deceleration Ramp Adaptation) active forces the Altivar ATV320 or ATV630 to stretch DEC automatically before the braking chopper fires around 785 V DC, keeping the external resistor cold while stop times drag out.

How do I tell SCF1 and SCF3 apart on an Altivar ATV320 or ATV630?

SCF1 flags a phase-to-phase short circuit across motor terminals U/T1, V/T2, and W/T3 (or low-inductance tuning error), whereas SCF3 flags a phase-to-earth ground fault or excessive shielded cable leakage. Disconnect motor cables and run both an under-2% (<2%) phase-to-phase resistance check for SCF1 and a 1,000 V DC phase-to-ground megger test for SCF3.

Why does my Altivar drive trip on OCF right after running tUn auto-tuning?

Running tUn on a hot motor at 90 °C to 100 °C stores inflated stator resistance into the Altivar motor model, or entering wrong nPr/UnS/nCr nameplate data skews magnetizing current. Let the motor cool to ambient 20 °C, verify star-delta terminal links against 400 V mains, re-enter exact nameplate specs, and repeat tUn at standstill.

Free tool for this topic

Electric Motor FLA, Starter & Overload Sizing CalculatorCalculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Open calculator

Continue learning

More on Motors, Drives and Electrical

View all →
Sponsored
Jignesh S Panchal
Technical Editorial Author Verified Editor

Jignesh S Panchal

Founder — Jaadu Digital & Musafir Infotech · 9+ Years in Industrial B2B

Jignesh S Panchal is the founder of Jaadu Digital and Musafir Infotech, and the publisher behind EngiTech. With over 9 years of hands-on experience in industrial marketing and B2B growth, he works closely with machinery OEMs, process equipment manufacturers, and industrial service providers across thermal processing, fluid handling, automation, packaging, and plant reliability. Combining deep practical knowledge of industrial manufacturing with how technical buyers actually evaluate equipment, he built EngiTech to give plant engineers and procurement teams reliable sizing tools, fault diagnostics, and verified B2B supplier discovery.

Your saved guides

Saved only in this browser. No account required.

Advertisement