PT100 RTD Resistance Table (IEC 60751, -200°C to +850°C) & Type K/J mV Chart

IEC 60751 PT100 & PT1000 RTD resistance table (-200°C to +850°C) with Callendar-Van Dusen math, °F, Type K & Type J thermocouple mV chart + live calculator.

Showing 53 of 53 IEC 60751 temperature points

Temp (°C) Temp (°F) PT100 (Ω) PT1000 (Ω) Type K (mV) Type J (mV)
-200 °C -328.0 °F 18.52 185.2 -5.891 -7.890
-180 °C -292.0 °F 27.10 271.0 -5.550 -7.403
-160 °C -256.0 °F 35.54 355.4 -5.141 -6.821
-140 °C -220.0 °F 43.88 438.8 -4.669 -6.159
-120 °C -184.0 °F 52.11 521.1 -4.138 -5.426
-100 °C -148.0 °F 60.26 602.6 -3.554 -4.633
-80 °C -112.0 °F 68.33 683.3 -2.920 -3.786
-60 °C -76.0 °F 76.33 763.3 -2.243 -2.893
-40 °C -40.0 °F 84.27 842.7 -1.527 -1.961
-20 °C -4.0 °F 92.16 921.6 -0.778 -0.995
0 °C 32.0 °F 100.00 1,000.0 0.000 0.000
20 °C 68.0 °F 107.79 1,077.9 0.798 1.019
25 °C 77.0 °F 109.73 1,097.3 1.000 1.277
40 °C 104.0 °F 115.54 1,155.4 1.612 2.059
60 °C 140.0 °F 123.24 1,232.4 2.436 3.116
80 °C 176.0 °F 130.90 1,309.0 3.267 4.187
100 °C 212.0 °F 138.51 1,385.1 4.096 5.269
120 °C 248.0 °F 146.07 1,460.7 4.920 6.360
140 °C 284.0 °F 153.58 1,535.8 5.735 7.459
160 °C 320.0 °F 161.05 1,610.5 6.540 8.562
180 °C 356.0 °F 168.48 1,684.8 7.338 9.669
200 °C 392.0 °F 175.86 1,758.6 8.138 10.779
220 °C 428.0 °F 183.19 1,831.9 8.940 11.889
240 °C 464.0 °F 190.47 1,904.7 9.747 13.000
260 °C 500.0 °F 197.71 1,977.1 10.561 14.110
280 °C 536.0 °F 204.90 2,049.0 11.382 15.219
300 °C 572.0 °F 212.05 2,120.5 12.209 16.327
320 °C 608.0 °F 219.15 2,191.5 13.040 17.434
340 °C 644.0 °F 226.21 2,262.1 13.874 18.538
360 °C 680.0 °F 233.21 2,332.1 14.713 19.642
380 °C 716.0 °F 240.18 2,401.8 15.554 20.745
400 °C 752.0 °F 247.09 2,470.9 16.397 21.848
420 °C 788.0 °F 253.96 2,539.6 17.243 22.952
440 °C 824.0 °F 260.78 2,607.8 18.091 24.057
460 °C 860.0 °F 267.56 2,675.6 18.941 25.164
480 °C 896.0 °F 274.29 2,742.9 19.792 26.276
500 °C 932.0 °F 280.98 2,809.8 20.644 27.393
520 °C 968.0 °F 287.62 2,876.2 21.497 28.516
540 °C 1,004.0 °F 294.21 2,942.1 22.350 29.647
560 °C 1,040.0 °F 300.75 3,007.5 23.203 30.788
580 °C 1,076.0 °F 307.25 3,072.5 24.055 31.939
600 °C 1,112.0 °F 313.71 3,137.1 24.905 33.102
620 °C 1,148.0 °F 320.12 3,201.2 25.755 34.279
640 °C 1,184.0 °F 326.48 3,264.8 26.602 35.470
660 °C 1,220.0 °F 332.79 3,327.9 27.447 36.675
680 °C 1,256.0 °F 339.06 3,390.6 28.289 37.893
700 °C 1,292.0 °F 345.28 3,452.8 29.129 39.132
720 °C 1,328.0 °F 351.46 3,514.6 29.965 40.388
740 °C 1,364.0 °F 357.59 3,575.9 30.798 41.657
760 °C 1,400.0 °F 363.67 3,636.7 31.628 42.919
780 °C 1,436.0 °F 369.71 3,697.1 32.453 N/A (>760°C)
800 °C 1,472.0 °F 375.70 3,757.0 33.275 N/A (>760°C)
850 °C 1,562.0 °F 390.48 3,904.8 35.313 N/A (>760°C)
Live Interactive Calculator · SI Metric & US Imperial

PT100 RTD & Thermocouple Resistance / mV Calculator

Convert process temperature to IEC 60751 PT100/PT1000 resistance (Ω) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.

Free engineering tool
Formula, worked example and FAQs below · results update as you type

°C

°C

°C


Results

RTD resistance
—
Ω

Thermocouple EMF (vs 0 °C)
—
mV

4–20 mA transmitter output
—
mA

Class A / Class 1 tolerance (±)
—
°C

Class B / Class 2 tolerance (±)
—
°C

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

Advertisement

Embed this free tool on your website or blog

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Frequently Asked Questions

What is the IEC 60751 resistance of a PT100 sensor at 0°C and 100°C?

Per IEC 60751 (alpha = 0.00385 Ohm/Ohm/°C), a standard PT100 RTD reads exactly 100.00 Ohm at 0°C and 138.51 Ohm at 100°C (a PT1000 reads 1,000.00 Ohm and 1,385.06 Ohm).

Why do industrial plants use 3-wire or 4-wire PT100 RTDs instead of 2-wire?

Every 0.385 Ohm of copper lead-wire resistance introduces roughly 1°C of positive measurement error on a PT100. 3-wire compensation cancels matched lead resistance, while 4-wire Kelvin measurement eliminates lead resistance completely.

When should I choose a Type K or Type J thermocouple over a PT100 RTD?

Use PT100 RTDs for high accuracy and stability from -200°C to +600°C (up to 850°C). Use Type J (up to 760°C) or Type K (up to 1,260°C) thermocouples for high-temperature furnaces, kilns, exhaust ducts, and fast response.