IEC 60751 PT100 & PT1000 RTD resistance table (-200°C to +850°C) with Callendar-Van Dusen math, °F, Type K & Type J thermocouple mV chart + live calculator.
Showing 53 of 53 IEC 60751 temperature points
| Temp (°C) | Temp (°F) | PT100 (Ω) | PT1000 (Ω) | Type K (mV) | Type J (mV) |
|---|---|---|---|---|---|
| -200 °C | -328.0 °F | 18.52 | 185.2 | -5.891 | -7.890 |
| -180 °C | -292.0 °F | 27.10 | 271.0 | -5.550 | -7.403 |
| -160 °C | -256.0 °F | 35.54 | 355.4 | -5.141 | -6.821 |
| -140 °C | -220.0 °F | 43.88 | 438.8 | -4.669 | -6.159 |
| -120 °C | -184.0 °F | 52.11 | 521.1 | -4.138 | -5.426 |
| -100 °C | -148.0 °F | 60.26 | 602.6 | -3.554 | -4.633 |
| -80 °C | -112.0 °F | 68.33 | 683.3 | -2.920 | -3.786 |
| -60 °C | -76.0 °F | 76.33 | 763.3 | -2.243 | -2.893 |
| -40 °C | -40.0 °F | 84.27 | 842.7 | -1.527 | -1.961 |
| -20 °C | -4.0 °F | 92.16 | 921.6 | -0.778 | -0.995 |
| 0 °C | 32.0 °F | 100.00 | 1,000.0 | 0.000 | 0.000 |
| 20 °C | 68.0 °F | 107.79 | 1,077.9 | 0.798 | 1.019 |
| 25 °C | 77.0 °F | 109.73 | 1,097.3 | 1.000 | 1.277 |
| 40 °C | 104.0 °F | 115.54 | 1,155.4 | 1.612 | 2.059 |
| 60 °C | 140.0 °F | 123.24 | 1,232.4 | 2.436 | 3.116 |
| 80 °C | 176.0 °F | 130.90 | 1,309.0 | 3.267 | 4.187 |
| 100 °C | 212.0 °F | 138.51 | 1,385.1 | 4.096 | 5.269 |
| 120 °C | 248.0 °F | 146.07 | 1,460.7 | 4.920 | 6.360 |
| 140 °C | 284.0 °F | 153.58 | 1,535.8 | 5.735 | 7.459 |
| 160 °C | 320.0 °F | 161.05 | 1,610.5 | 6.540 | 8.562 |
| 180 °C | 356.0 °F | 168.48 | 1,684.8 | 7.338 | 9.669 |
| 200 °C | 392.0 °F | 175.86 | 1,758.6 | 8.138 | 10.779 |
| 220 °C | 428.0 °F | 183.19 | 1,831.9 | 8.940 | 11.889 |
| 240 °C | 464.0 °F | 190.47 | 1,904.7 | 9.747 | 13.000 |
| 260 °C | 500.0 °F | 197.71 | 1,977.1 | 10.561 | 14.110 |
| 280 °C | 536.0 °F | 204.90 | 2,049.0 | 11.382 | 15.219 |
| 300 °C | 572.0 °F | 212.05 | 2,120.5 | 12.209 | 16.327 |
| 320 °C | 608.0 °F | 219.15 | 2,191.5 | 13.040 | 17.434 |
| 340 °C | 644.0 °F | 226.21 | 2,262.1 | 13.874 | 18.538 |
| 360 °C | 680.0 °F | 233.21 | 2,332.1 | 14.713 | 19.642 |
| 380 °C | 716.0 °F | 240.18 | 2,401.8 | 15.554 | 20.745 |
| 400 °C | 752.0 °F | 247.09 | 2,470.9 | 16.397 | 21.848 |
| 420 °C | 788.0 °F | 253.96 | 2,539.6 | 17.243 | 22.952 |
| 440 °C | 824.0 °F | 260.78 | 2,607.8 | 18.091 | 24.057 |
| 460 °C | 860.0 °F | 267.56 | 2,675.6 | 18.941 | 25.164 |
| 480 °C | 896.0 °F | 274.29 | 2,742.9 | 19.792 | 26.276 |
| 500 °C | 932.0 °F | 280.98 | 2,809.8 | 20.644 | 27.393 |
| 520 °C | 968.0 °F | 287.62 | 2,876.2 | 21.497 | 28.516 |
| 540 °C | 1,004.0 °F | 294.21 | 2,942.1 | 22.350 | 29.647 |
| 560 °C | 1,040.0 °F | 300.75 | 3,007.5 | 23.203 | 30.788 |
| 580 °C | 1,076.0 °F | 307.25 | 3,072.5 | 24.055 | 31.939 |
| 600 °C | 1,112.0 °F | 313.71 | 3,137.1 | 24.905 | 33.102 |
| 620 °C | 1,148.0 °F | 320.12 | 3,201.2 | 25.755 | 34.279 |
| 640 °C | 1,184.0 °F | 326.48 | 3,264.8 | 26.602 | 35.470 |
| 660 °C | 1,220.0 °F | 332.79 | 3,327.9 | 27.447 | 36.675 |
| 680 °C | 1,256.0 °F | 339.06 | 3,390.6 | 28.289 | 37.893 |
| 700 °C | 1,292.0 °F | 345.28 | 3,452.8 | 29.129 | 39.132 |
| 720 °C | 1,328.0 °F | 351.46 | 3,514.6 | 29.965 | 40.388 |
| 740 °C | 1,364.0 °F | 357.59 | 3,575.9 | 30.798 | 41.657 |
| 760 °C | 1,400.0 °F | 363.67 | 3,636.7 | 31.628 | 42.919 |
| 780 °C | 1,436.0 °F | 369.71 | 3,697.1 | 32.453 | N/A (>760°C) |
| 800 °C | 1,472.0 °F | 375.70 | 3,757.0 | 33.275 | N/A (>760°C) |
| 850 °C | 1,562.0 °F | 390.48 | 3,904.8 | 35.313 | N/A (>760°C) |
No matching rows found. Clear the search box or switch back to All.
PT100 RTD & Thermocouple Resistance / mV Calculator
Convert process temperature to IEC 60751 PT100/PT1000 resistance (Ω) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.
Frequently Asked Questions
What is the IEC 60751 resistance of a PT100 sensor at 0°C and 100°C?
Per IEC 60751 (alpha = 0.00385 Ohm/Ohm/°C), a standard PT100 RTD reads exactly 100.00 Ohm at 0°C and 138.51 Ohm at 100°C (a PT1000 reads 1,000.00 Ohm and 1,385.06 Ohm).
Why do industrial plants use 3-wire or 4-wire PT100 RTDs instead of 2-wire?
Every 0.385 Ohm of copper lead-wire resistance introduces roughly 1°C of positive measurement error on a PT100. 3-wire compensation cancels matched lead resistance, while 4-wire Kelvin measurement eliminates lead resistance completely.
When should I choose a Type K or Type J thermocouple over a PT100 RTD?
Use PT100 RTDs for high accuracy and stability from -200°C to +600°C (up to 850°C). Use Type J (up to 760°C) or Type K (up to 1,260°C) thermocouples for high-temperature furnaces, kilns, exhaust ducts, and fast response.