3-phase AC motor FLA chart (0.37–315 kW / 0.5–400 HP) with IEC & NEMA frame sizes, 400V/415V/460V amps, DOL/Star-Delta breakers & live FLA/cable calculator.
Showing 25 of 25 3-phase motor ratings
| Power (kW) | Power (HP) | IEC Frame | NEMA Frame | FLA @ 400V (A) | FLA @ 415V (A) | FLA @ 460V (A) | Typical Breaker & Starter |
|---|---|---|---|---|---|---|---|
| 0.37 kW | 0.5 HP | 71 | 56 | 1.05 | 1.01 | 0.92 | 2 A MCB / DOL |
| 0.55 kW | 0.75 HP | 80 | 56 | 1.48 | 1.43 | 1.29 | 2.5 A MCB / DOL |
| 0.75 kW | 1 HP | 80 | 143T | 1.88 | 1.81 | 1.64 | 4 A MCB / DOL |
| 1.1 kW | 1.5 HP | 90S | 145T | 2.60 | 2.51 | 2.26 | 6 A MCB / DOL |
| 1.5 kW | 2 HP | 90L | 145T | 3.40 | 3.28 | 2.96 | 6 A MCB / DOL |
| 2.2 kW | 3 HP | 100L | 182T | 4.80 | 4.63 | 4.17 | 10 A MCB / DOL |
| 3.0 kW | 4 HP | 100L | 184T | 6.40 | 6.17 | 5.57 | 10 A MCB / DOL |
| 3.7 kW | 5 HP | 112M | 184T | 7.80 | 7.52 | 6.78 | 16 A MCB / DOL |
| 5.5 kW | 7.5 HP | 132S | 213T | 11.2 | 10.8 | 9.7 | 20 A MCB / DOL |
| 7.5 kW | 10 HP | 132M | 215T | 15.0 | 14.5 | 13.0 | 25 A MCCB / Star-Delta |
| 11 kW | 15 HP | 160M | 254T | 21.5 | 20.7 | 18.7 | 32 A MCCB / Star-Delta |
| 15 kW | 20 HP | 160L | 256T | 28.5 | 27.5 | 24.8 | 40 A MCCB / Star-Delta |
| 18.5 kW | 25 HP | 180M | 284T | 35.0 | 33.7 | 30.4 | 50 A MCCB / Star-Delta |
| 22 kW | 30 HP | 180L | 286T | 41.0 | 39.5 | 35.7 | 63 A MCCB / Star-Delta |
| 30 kW | 40 HP | 200L | 324T | 55.0 | 53.0 | 47.8 | 80 A MCCB / Star-Delta |
| 37 kW | 50 HP | 225S | 326T | 68.0 | 65.5 | 59.1 | 100 A MCCB / Star-Delta |
| 45 kW | 60 HP | 225M | 364T | 82.0 | 79.0 | 71.3 | 125 A MCCB / Star-Delta |
| 55 kW | 75 HP | 250M | 365T | 99.0 | 95.4 | 86.1 | 160 A MCCB / Star-Delta or VFD |
| 75 kW | 100 HP | 280S | 404T | 134 | 129 | 117 | 200 A MCCB / Star-Delta or VFD |
| 90 kW | 125 HP | 280M | 405T | 160 | 154 | 139 | 250 A MCCB / Star-Delta or VFD |
| 110 kW | 150 HP | 315S | 444T | 195 | 188 | 170 | 250 A MCCB / Soft-Starter or VFD |
| 132 kW | 175 HP | 315M | 445T | 232 | 224 | 202 | 315 A MCCB / Soft-Starter or VFD |
| 160 kW | 200 HP | 315L | 445T | 280 | 270 | 243 | 400 A MCCB / Soft-Starter or VFD |
| 200 kW | 250 HP | 315L | 447T | 348 | 335 | 303 | 500 A MCCB / Soft-Starter or VFD |
| 315 kW | 400 HP | 355L | 5000 | 542 | 522 | 471 | 800 A ACB / Soft-Starter or VFD |
No matching rows found. Clear the search box or switch back to All.
Electric Motor FLA, Starter & Overload Sizing Calculator
Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.
Frequently Asked Questions
How is 3-phase electric motor full-load current (FLA) calculated from kW?
FLA = (P_kW x 1000) / (1.732 x V_line x efficiency x power_factor). As a field rule of thumb at 400-415 V (PF ~0.85, eff ~90%), 3-phase motor FLA is approximately 1.8 x kW (or ~1.35 x HP).
At what motor kW should I switch from DOL to Star-Delta or VFD/Soft Starter?
Most industrial plants allow Direct-On-Line (DOL) starting up to 5.5-7.5 kW where grid transformer capacity permits. Above 7.5-11 kW, Star-Delta, soft starter, or VFD starting limits 6-7x locked-rotor inrush.
How do IEC frame sizes map to NEMA motor frame designations?
Both standards fix shaft height and mounting footprint: IEC 80 ≈ NEMA 56/143T (0.75 kW / 1 HP), IEC 132 ≈ NEMA 213T-215T (5.5-7.5 kW), IEC 160 ≈ NEMA 254T-256T (11-15 kW), and IEC 225 ≈ NEMA 326T-364T (37-45 kW).