# Saturated Steam Table & Calculator \(bar / psi / °C / °F — Enthalpy & Latent Heat\)

> Convert bar g, bar a, psig, psia, °C, or °F to saturation temperature, sensible heat hf, latent heat hfg, total enthalpy hg, and specific volume vg.

Canonical: https://engitech.in/saturated-steam-table-pressure-temperature-calculator/ | Published: 2026-11-20 | Updated: 2026-11-20

Interactive IAPWS saturated steam table and calculator. Convert bar g, bar a, psig, psia, °C, and °F to saturation temp, hf, latent heat hfg, hg, and vg.

Solve From

Input Value

Local Atmospheric (bar a)

Saturation Temp (Tsat)**—***—*

Abs / Gauge Pressure**—***—*

Sensible Heat (hf)**—***—*

Latent Heat (hfg)**—***—*

Total Enthalpy (hg)**—***—*

Specific Volume (vg)**—***—*

IAPWS-IF97 Region 4 Saturated Steam State

Filter steam table

| Abs (bar a) | Gauge (bar g) | Abs (psia) | Temp (°C / °F) | hf (kJ/kg) | Latent hfg (kJ/kg) | Total hg (kJ/kg) | vg (m³/kg) |
| --- | --- | --- | --- | --- | --- | --- | --- |

**EngiTech — engitech.in**Saturated Steam Table & Calculator (bar / psi / °C / °F — Enthalpy & Latent Heat)

**Embed this free tool on your website or blog**

Free to embed on engineering blogs, university guides, and plant wikis (zero login required).

Distribute steam at high pressure to shrink header pipe size, then reduce right before heat exchangers or dryers.

## Why Running Dryers at 10 bar Often Wastes Fuel

Plant operators frequently crank boiler pressure from 4 bar g to 10 bar g hoping a [rotary dryer](https://engitech.in/rotary-dryer-shell-sizing-holdup-retention/) or jacketed kettle will run faster. Yes, saturation temperature jumps from 152 °C to 184 °C, boosting wall delta-T. But latent heat *hfg* drops by 109 kJ/kg while hot condensate flashes violently across undersized steam traps.

Check your [steam system efficiency](https://engitech.in/steam-system-efficiency-guide/) and verify steam line velocity using our [ASME B36.10 Pipe Schedule Chart](https://engitech.in/asme-b36-10-pipe-schedule-40-80-dimensions-chart/) (target 20-35 m/s for saturated headers).

## Flash Steam & Temperature Sensor Checks

Flash % = (hf_in - hf_out) / hfg_out × 100

Always verify header saturation temperature with a calibrated thermowell sensor—if your gauge reads 6 bar g (165 °C saturated) but a [PT100 RTD sensor](https://engitech.in/pt100-rtd-resistance-table-iec-60751-chart/) reads 185 °C, you have superheated steam from a pressure-reducing valve and need desuperheating water before jacketed vessels. Match flange ratings on our [ASME B16.5 Flange Chart](https://engitech.in/asme-b16-5-flange-dimensions-chart-class-150-300/).

## Frequently Asked Questions

**What is the difference between bar g (gauge) and bar a (absolute) in steam tables?**

Steam tables are indexed by absolute pressure (bar a or psia), where 0 bar a is a full vacuum. A plant pressure gauge reads bar g above local atmosphere (~1.01325 bar / 14.696 psi). Always add 1.01325 bar to bar g before reading steam properties.

**Why does latent heat (hfg) drop as steam pressure goes up?**

At 1 bar g (120.2 °C), condensing 1 kg of steam releases 2,201.6 kJ. At 10 bar g (184.1 °C), latent heat drops to 1,998.5 kJ/kg while condensate enthalpy hf rises. Higher pressure raises temperature head (delta-T), not energy per kg of steam.

**Why do steam-heated dryers and reactors trap-lock or lose heat at higher header pressure?**

Raising pressure above design floods undersized steam traps with flash steam and cuts latent heat per kg. Unless your process actually needs higher wall temperature, running at the lowest steady pressure that meets heat duty saves boiler fuel.

**How do I quickly estimate flash steam percentage from condensate?**

Flash % = (hf_high - hf_low) / hfg_low x 100. Dropping 8 bar g condensate into a 1 bar g flash vessel releases roughly 13% of the condensate mass as usable low-pressure steam.

![Jignesh S Panchal](https://engitech.in/wp-content/uploads/2026/11/jignesh-s-panchal-author.jpg)

Technical Editorial Author Verified Editor

## Jignesh S Panchal

Founder — Jaadu Digital & Musafir Infotech · 9+ Years in Industrial B2B

Jignesh S Panchal is the founder of Jaadu Digital and Musafir Infotech, and the publisher behind EngiTech. With over 9 years of hands-on experience in industrial marketing and B2B growth, he works closely with machinery OEMs, process equipment manufacturers, and industrial service providers across thermal processing, fluid handling, automation, packaging, and plant reliability. Combining deep practical knowledge of industrial manufacturing with how technical buyers actually evaluate equipment, he built EngiTech to give plant engineers and procurement teams reliable sizing tools, fault diagnostics, and verified B2B supplier discovery.

[LinkedIn](https://www.linkedin.com/in/jignesh-s-panchal/) [All Guides by Author →](https://engitech.in/author/jignesh-panchal/) [Editorial standards](https://engitech.in/editorial-standards-and-corrections/)