# PT100 RTD & Thermocouple Resistance / mV Calculator

> Convert process temperature to IEC 60751 PT100/PT1000 resistance \(Ω\) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.

Canonical: https://engitech.in/pt100-rtd-thermocouple-calculator/ | Published: 2026-11-18 | Updated: 2026-11-18

Convert process temperature to IEC 60751 PT100/PT1000 resistance (Ω) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.

Free engineering tool Formula, worked example and FAQs below · results update as you type

Results

**RTD resistance**

—

Ω

**Thermocouple EMF (vs 0 °C)**

—

mV

**4–20 mA transmitter output**

—

mA

**Class A / Class 1 tolerance (±)**

—

°C

**Class B / Class 2 tolerance (±)**

—

°C

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

## Formula used

IEC 60751 Callendar–Van Dusen (T ≥ 0 °C): **R(T)** = R0 × (1 + A·T + B·T²), where A = 3.9083×10−3 °C−1 and B = −5.775×10−7 °C−2.

4–20 mA loop current: **I** = 4 + 16 × (T − LRV) ÷ (URV − LRV). Class A RTD tolerance: ±(0.15 + 0.002|T|) °C.

## How to use this calculator

1. Choose PT100, PT1000, Type K or Type J sensor.
2. Enter the measured process temperature in °C.
3. Enter the transmitter 4 mA (LRV) and 20 mA (URV) range values.
4. Compare resistance/mV and loop current against your multimeter or HART calibrator.

## Worked example

A PT100 sensor at **150 °C** reads **157.33 Ω** (±0.45 °C Class A). On a 0–300 °C transmitter span, the loop current is **12.00 mA**.

## Frequently asked questions

**When should I choose a 3-wire or 4-wire PT100 over 2-wire?**

Use 3-wire RTDs for standard industrial PLC/transmitter runs to cancel lead resistance, and 4-wire RTDs for precision lab or custody-transfer measurements where every 0.385 Ω lead error shifts temperature by 1 °C.

**Does cold-junction compensation matter when checking thermocouple mV?**

Yes. The table value assumes a 0 °C reference junction. If your field terminal block is at 30 °C ambient, subtract the mV equivalent of 30 °C (~1.20 mV for Type K) when measuring with a plain millivoltmeter.

**What is the difference between PT100 Class A and Class B?**

Class A is roughly twice as accurate (±0.15 + 0.002|T| °C) as Class B (±0.30 + 0.005|T| °C) and is preferred for critical reactor, pasteurizer and HVAC chiller loops.

## More free engineering tools

[**Power Factor Correction (kVAR) Calculator**Capacitor kVAR needed to improve power factor, with kVA and current before and after correction.](https://engitech.in/power-factor-correction-calculator/)[**Cable Voltage Drop Calculator (IEC 60228)**Voltage drop, percentage drop and power loss for copper and aluminium LV cables using IEC 60228 conductor resistance corrected to operating temperature.](https://engitech.in/cable-voltage-drop-calculator/)[**Motor Running Cost & Energy Calculator**Electrical input power, annual energy use and running cost of a motor from its rating, load, efficiency and operating hours.](https://engitech.in/motor-running-cost-calculator/)[**Electric Motor FLA, Starter & Overload Sizing Calculator**Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.](https://engitech.in/electric-motor-fla-starter-calculator/)[**Transformer kVA Sizing & Fault Current Calculator**Size a three-phase distribution transformer in kVA from plant load, demand factor, power factor and growth margin, plus HV/LV currents and secondary 3-phase short-circuit current Isc.](https://engitech.in/transformer-kva-short-circuit-calculator/)[**Motor Torque, Power & Current Calculator**Convert motor power and speed to shaft torque, or torque to power, and estimate full-load current for three-phase and single-phase motors.](https://engitech.in/motor-torque-power-calculator/)