# Electric Motor FLA, Starter & Overload Sizing Calculator

> Calculate full-load current \(FLA\), starting peak current by starter type \(DOL, Star-Delta, Soft-Starter, VFD\), thermal overload setting and minimum contactor rating.

Canonical: https://engitech.in/electric-motor-fla-starter-calculator/ | Published: 2026-11-18 | Updated: 2026-11-18

Calculate full-load current (FLA), starting peak current by starter type (DOL, Star-Delta, Soft-Starter, VFD), thermal overload setting and minimum contactor rating.

Free engineering tool Formula, worked example and FAQs below · results update as you type

Results

**Full-load current (FLA)**

—

A

**Starting peak current**

—

A

**Overload relay setting (1.05× FLA)**

—

A

**Min. AC-3 contactor rating (1.25× FLA)**

—

A

**Input apparent power**

—

kVA

Results are engineering estimates for preliminary design. Verify critical values with codes, vendor data or a qualified engineer.

## Formula used

Three-phase **FLA** = (PkW × 1000) ÷ (√3 × V × cos φ × η). Single-phase removes the √3 factor.

Starting peak current depends on starter: DOL ≈ 6.5× FLA, Soft-Starter ≈ 3.0×, Star-Delta ≈ 2.2×, VFD ≈ 1.5×.

## How to use this calculator

1. Select 3-phase or 1-phase supply and enter motor shaft kW/HP.
2. Enter supply voltage, nameplate power factor and efficiency.
3. Choose the starting method to compare inrush amps and contactor sizing.
4. Size feeder cables using our <a href="/cable-voltage-drop-calculator/">Cable Sizing & Voltage Drop Calculator</a>.

## Worked example

A 15 kW, 415 V, 3-phase motor (cos φ = 0.85, η = 91 %) draws **27.0 A** FLA. With Star-Delta starting, peak line current drops from 175 A (DOL) to **59.4 A**; set overload around **28.3 A**.

## Frequently asked questions

**Where should the thermal overload relay be placed in a Star-Delta starter?**

If installed inside the delta branch (with the main contactor), set the relay to 0.58 × FLA (FLA ÷ √3). If installed on the main incoming line, set it to 1.0–1.05 × FLA.

**At what motor power do plants switch from DOL to Star-Delta or Soft-Starter?**

Most industrial plants restrict DOL starting to 7.5–11 kW on 415 V grids to avoid voltage dip on adjacent drives and switchgear.

**Why use AC-3 contactor ratings for motors?**

IEC AC-3 duty covers breaking full-load or stalled squirrel-cage motor currents safely; resistive AC-1 ratings cannot handle motor inductive switching arcs.

## More free engineering tools

[**Power Factor Correction (kVAR) Calculator**Capacitor kVAR needed to improve power factor, with kVA and current before and after correction.](https://engitech.in/power-factor-correction-calculator/)[**Cable Voltage Drop Calculator (IEC 60228)**Voltage drop, percentage drop and power loss for copper and aluminium LV cables using IEC 60228 conductor resistance corrected to operating temperature.](https://engitech.in/cable-voltage-drop-calculator/)[**Motor Running Cost & Energy Calculator**Electrical input power, annual energy use and running cost of a motor from its rating, load, efficiency and operating hours.](https://engitech.in/motor-running-cost-calculator/)[**PT100 RTD & Thermocouple Resistance / mV Calculator**Convert process temperature to IEC 60751 PT100/PT1000 resistance (Ω) or Type K/J thermocouple millivolts, plus 4–20 mA transmitter loop output and Class A/B tolerance.](https://engitech.in/pt100-rtd-thermocouple-calculator/)[**Transformer kVA Sizing & Fault Current Calculator**Size a three-phase distribution transformer in kVA from plant load, demand factor, power factor and growth margin, plus HV/LV currents and secondary 3-phase short-circuit current Isc.](https://engitech.in/transformer-kva-short-circuit-calculator/)[**Motor Torque, Power & Current Calculator**Convert motor power and speed to shaft torque, or torque to power, and estimate full-load current for three-phase and single-phase motors.](https://engitech.in/motor-torque-power-calculator/)

[All calculators →](https://engitech.in/engineering-tools/)